并联补偿电容器用无间隙金属氧化物避雷器
电容器型是用于抑制真空开关或少油开关操作电容器组产生的过电压,保护电容器组免受操作过电压的损坏。
| 系统
标称
电压
kV
(有效值)
| 避雷器额 定 电 压 kV
(有效值)
| 避雷器持续运行电压
kV
(有效值)
| 直 流1mA参考电压
kV
(有效值)
| 2ms
方波通流容量
A
| 残 压
| 伞 径
φ
mm
| 高 度
H
mm
| 雷电冲
击电流
| 操作冲
击电流
| KV (峰值) ≯
| Y5WR-5/13.5
| 3
| 5
| 4.0
| 7.2
| 400
| 13.5
| 10.5
| 100
| 220
| YH5WR-5/13.5
| 100
| 200
| Y5WR-10/27
| 6
| 10
| 8.0
| 14.4
| 400
| 27.0
| 21.0
| 100
| 220
| YH5WR-10/27
| 100
| 200
| YH5WR-10/27DL
| 100
| 200
| Y5WR-12/32..4
| 10
| 12
| 9.6
| 17.4
| 400
| 32.4
| 25.2
| 100
| 270
| YH5WR-12/32..4
| 100
| 257
| YH5WR-12/32..4DL
| 100
| 257
| Y5WR-15/40.5
| 10
| 15
| 12.0
| 21.8
| 400
| 40.5
| 31.5
| 100
| 270
| YH5WR-15/40.5
| 100
| 257
| YH5WR-15/40.5DL
| 100
| 257
| Y5WR-17/45
| 10
| 17
| 13.6
| 24.0
| 400
| 45.0
| 35.0
| 100
| 270
| YH5WR-17/45
| 100
| 257
| YH5WR-17/45DL
| 100
| 257
| Y5WR-51/134
| 35
| 51
| 40.8
| 73.0
| 400
| 134
| 105.0
| 232
| 1080
| YH5WR-51/134
| 170
| 620
| YH5WR-51/134DL
| 110
| 620
| Y5WR-52.7/134
| 35
| 52.7
| 41
| 74.0
| 400
| 134.0
| 105.0
| 232
| 1080
| YH5WR-52.7/134
| 170
| 620
| YH5WR-52.7/134DL
| 110
| 620
|
|