6B12 / 6B12HV
Rev. 0 | Page 3 of 8
Models 6B12 and 6B12HV
Range Description
(Software Configurable)
Accuracy
(Typical)
Error
(Maximum)
Noise
(Peak-to-Peak)
±150 mV
±0.03 % FS
±0.06 % FS
±0.02 % FS
±500 mV
±0.01 % FS
±0.04 % FS
±0.008 % FS
±1 V
±0.006 % FS
±0.03 % FS
±0.007 % FS
±5 V
±0.006 % FS
±0.03 % FS
±0.006 % FS
±10 V
±0.006 % FS
±0.03 % FS
±0.005 % FS
±50 V
±0.006 % FS
±0.03 % FS
±0.004 % FS
±20 mA1
±0.006 % FS2
±0.03 % FS2
±0.007 % FS
1 This range requires the use of a 50
current-to-voltage conversion resistor, model AC1381.
2 Does not include the error of the current-to-voltage input resistor, Model AC1381.
6B12 and 6B12HV Specifications
(typical @ +25°C and Vs = +5 V dc)
Description
Model 6B12 and 6B12HV
Inputs, Software Selectable
Voltage Ranges
mV
±150 mV; ±500 mV
Volt
±1 V; ±5 V; ±10 V; ±50 V
Current Range
±20 mA
Communications
Protocol
RS-485
Baud Rates, Software Selectable
300K, 600K, 1.2K, 2.4K, 9.6K, 19.2K
Accuracy
Initial @ +25°C
Refer to Model Table
Input Offset vs. Temperature
±0.3 V/°C
Span vs. Temperature
±10 ppm/°C (±50 ppm/°C, maximum)
Input Resistance
1 M
Bandwidth, -3 dB
4 Hz
Conversion Rate
9 samples /second
Synchronized Sampling Command
Yes
Conversion Time
70 ms maximum
Common-Mode Voltage (CMV)
Input-to-Output and Power
Model 6B12
1500 V rms, continuous
Model 6B12HV
2500 V rms, continuous
Common-Mode Rejection (CMR)
1 k
Source Imbalance @ 50/60 Hz
108 dB