2
Lineage Power
Data Sheet
March 2008
18 Vdc to 36 Vdc Inputs, 30 W
CC030-Series Power Modules; dc-dc Converters:
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are abso-
lute stress ratings only. Functional operation of the device is not implied at these or any other conditions in excess
of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for extended
periods can adversely affect device reliability.
Parameter
Symbol
Min
Max
Unit
Input Voltage (continuous)
VI
—
50
Vdc
Operating Case Temperature
(See Thermal Considerations section.)
TC
–40
100
°C
Storage Temperature
Tstg
–40
110
°C
I/O Isolation Voltage:
Continuous
Transient (1 min)
—
500
800
Vdc
V
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature
conditions.
Table 1. Input Specifications
Parameter
Symbol
Min
Typ
Max
Unit
Operating Input Voltage
VI
18
24
36
Vdc
Maximum Input Current
(VI = 0 V to 75 V; IO = IO, max; see Figure 1.) II, max
—
3.0
A
Inrush Transient
i2t
—
0.2
A2s
Input Reflected-Ripple Current, Peak-to-Peak
(0.5 Hz to 20 MHz, 12 source impedance;
see Figure
14 and Design Considerations.)
II
—
30
—
mAp-p
Input Ripple Rejection (120 Hz)
—
60
—
dB
Fusing Considerations
CAUTION: This power module is not internally fused. An input line fuse must always be used.
This encapsulated power module can be used in a wide variety of applications, ranging from simple stand-alone
operation to an integrated part of a sophisticated power architecture. To preserve maximum flexibility, internal fus-
ing is not included; however, to achieve maximum safety and system protection, always use an input line fuse. The
safety agencies require a normal-blow fuse with a maximum rating of 5 A in series with the input (see Safety Con-
siderations section). Based on the information provided in this data sheet on inrush energy and maximum dc input
current, the same type of fuse with a lower rating can be used. Refer to the fuse manufacturer’s data for further
information.