D.F.  =  VTx D.D.P.  =  7.0 x 1000  =  93.3
CUB4VSIGNALINPUT
The voltage range is selected by setting one of the DIP switches S1 to S4 for
the desired input voltage. The unit will indicate the direct readout for the range
selected.
Note: Only one Voltage Range switch (S1-S4) should be selected (ON).
The SCALE DIP switch (S5) and the Scaling Potentiometer are used when it
is necessary to scale the display to indicate other engineering units. The Scale
switch should be left in the “OFF” position when the application requires direct
voltage readout on the display.
The Calibration Potentiometer has been set at the factory and should not be
adjusted unless the unit is being re-calibrated with an accurate voltage source.
The power supply common and signal common are connected internally at
the same screw terminal marked COMM. The power supply common, and the
signal common must be at the same voltage potential. The voltmeter cannot
measure a voltage with a reference that is different than the power supply
common.
After the Division Factor for the application has been calculated, the proper
voltage range switch that will provide for the Division Factor is set to the “ON”
position. Use the “Division Factor Range Selection Chart” to choose the proper
DIP switch setting.
Note: Only one voltage DIP switch should be turned on. Set the switch before
the voltage signal is applied.
EXAMPLE: A relative humidity transducer delivers a 7.0 VDC voltage at a
relative humidity of 75%.
D.R. 75
This Division Factor is between 10.5 and 100.5, therefore DIP switch
position S3 is set to the “ON” position. The Scaling Potentiometer is then
adjusted for the desired readout at a known relative humidity.
BLOCK DIAGRAM CUB4V
VOLTAGE
SWITCHES
DECIMAL
POINTS
1
2
3
4
5
6
7
8
D.P.
3 SIG.+
1 COM
ON
1 2 3 4 5 6 7 8
RED LION CONTROLS
YORK, PA. MADE IN U.S.A.
V+ 2
CUB4V
Caution: The Maximum Voltage for each switch position must not be
exceeded or the unit may be damaged (See Specifications).
Caution: 9 to 28 VDC power circuit is not isolated from the
signal circuit.
VOLTMETER SCALING
In many industrial applications, a voltmeter is required to display a reading
in terms of PSI, RPM, or some other unit of measure. The signal voltage being
measured is normally generated by a transducer which senses the variable and
delivers a linear output voltage. To provide the desired readout at the specified
voltage, the voltmeter must be scaled. The Scale switch, when in the “ON”
position, enables the Scale Potentiometer. The Scale Potentiometer is used with
a voltage range to provide a method of scaling the unit. The voltage DIP
switches are used to select one of the four coarse Division Factor ranges and the
Scale Potentiometer is a fine scale adjustment within the selected range. The
chart below shows the division factor range associated with each range
selection switch.
DIVISION FACTOR RANGE SELECTION CHART
S1: 0-199.9 mVDC (0.1 D.F. 1.2)
S2: 0-1.999 VDC (1.2 D.F. 10.5)
S3: 0-19.99 VDC (10.5 D.F. 100.5)
S4: 0-199.9 VDC (100.5 D.F. 1300)
Note: Enabling the Scale Potentiometer does NOT affect the calibration of
the unit.
CUB4I SIGNAL INPUT
The CUB4 Current Meter has four current ranges that are selected by
positioning the jumper in the proper location on the male header strip.
The SCALE DIP switch (S1) and the Scaling Potentiometer are used when it
is necessary to scale the display to indicate other engineering units. The Scale
switch should be left in the “OFF” position when the application requires direct
current readout on the display.
When the power supply is floating (unreferenced) to the desired measurement
points, the (-) signal input and the power supply common should be connected.
If the power supply is not floating (referenced), the common mode voltage
between the (-) signal input and power supply common terminal must not be
greater than 1.0 V peak. A common mode voltage higher than 1.0 V peak will
result in a measurement error.
The Calibration Potentiometer has been set at the factory and should not be
adjusted unless the unit is being re-calibrated with an accurate current source.
To determine the proper voltage range for an application requiring scaling,
the “Division Factor” required to provide the proper display reading must first
be determined by using the following formula.
1
2
3
4
D.F = VT x D.D.P.
WHERE:
VT
D.D.P.
D.F.
D.R.
=
=
=
=
USING THE FORMULA:
D.R.
Maximum Transducer Output
Display Decimal Point
Division Factor
Desired Reading
3 SIG.-
1 COM
ON
1 2 3 4
199.9uA 19.99mA
1.999mA 199.9mA
RED LION CONTROLS
YORK, PA. MADE IN U.S.A.
SIG.+ 4
V+ 2
D.D.P.
0.000
00.00
000.0
0000
=
=
=
=
1
10
100
1000
The DISPLAY DECIMAL POINT (D.D.P.)
is determined by the desired decimal
point placement in the readout.
Caution: The Maximum Current for each jumper position must not
be exceeded or the unit may be damaged (See Specifications).
3
相关PDF资料
PDF描述
CUB4TC00 METER PANEL LCD THERMOCOUPLE
CUB5COM1 RS485 SERIAL COMMO CARD
CUB5IB00 DC METER RED/GREEN BKLT
CUB5PB00 PROCESS METER RED/GREEN BKLT
CUB5RTR0 RTD METER REFLECTIVE
相关代理商/技术参数
参数描述
CUB4L000 功能描述:COUNTER, REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 计数器 系列:* 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB4L010 功能描述:COUNTER W/YEL/GRN BKLTING RoHS:是 类别:工业控制,仪表 >> 计数器 系列:* 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB4L020 功能描述:COUNTER W/RED BKLTING RoHS:是 类别:工业控制,仪表 >> 计数器 系列:* 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB4L800 功能描述:8-DIGIT COUNTER, REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 计数器 系列:* 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB4L80M 制造商:Red Lion Controls 功能描述:COUNTER, REFLECTIVE W/V+ TERM 8-DIGIT 制造商:Red Lion Controls 功能描述:8-DIGIT COUNTER REFLECTIVE W/V+