参数资料
型号: CUB5VR00
厂商: Red Lion Controls
文件页数: 7/12页
文件大小: 0K
描述: METER LCD DC VOLT 8DIGIT
标准包装: 1
系列: *
其它名称: CUB5VR00-ND
Q6167506
RLC143
6.1 MODULE 1 - S IGNAL I NPUT P ARAMETERS ( 1-INP )
1-INP
SEL
PARAMETER MENU
Pro
rANGE
Input
Range
dECPt
Display
Decimal
Point
OFSEt
Display
Offset
Value
FILtr
Filter
Setting
bANd
Filter
Band
StYLE
Scaling
Style
INP 1
Input Value
for Scaling
Point 1
dSP 1
Display Value
For Scaling
Point 1
INP 2
Input Value
for Scaling
Point 2
dSP 2
Display Value
For Scaling
Point 2
USrIN
User Input
Function
U-ASN
User Input
Assignment
?
rAN6E
SELECTION
SELECTION
? 200u
OFSEt ?
CUB5VINPUTRANGE
RANGE RANGE
RESOLUTION RESOLUTION
0.2u 200.00 mV 20u 20.000 V
2u 2.0000 V 200u 200.00 V
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
DISPLAY DECIMAL POINT
dECPt ? 0                0.0              0.00            0.000          0.0000
? 0
Select the decimal point location for the Input, MIN and MAX displays. This
selection also affects the dSP1 and dSP2 parameters and setpoint values.
DISPLAY OFFSET VALUE
-19999 to 19999
? 0.00
The display can be corrected with an offset value. This can be used to
compensate for signal variations or sensor errors. This value is automatically
updated after a Zero Display to show how far the display is offset. A value of
zero will remove the effects of offset.
FILTER SETTING
FILtr ? 0,1    2    3
? 1
If the displayed value is difficult to read due to small process variations or
noise, increased levels of filtering will help to stabilize the display. Software
filtering effectively combines a fraction of the current input reading with a
fraction of the previous displayed reading to generate the new display.
Filter values represent no filtering (0), up to heavy filtering (3). A value of 1
for the filter uses 1/4 of the new input and 3/4 of the previous display to generate
the new display. A filter value of 2 uses 1/8 new and 7/8 previous. A filter value
of 3 uses 1/16 new and 15/16 previous.
FILTER BAND
bANd ? 0 to 199 display units
? 10
The filter will adapt to variations in the input signal. When the variation
exceeds the input filter band value, the filter disengages. When the variation
becomes less than the band value, the filter engages again. This allows for a
stable readout, but permits the display to settle rapidly after a large process
change. The value of the band is in display units, independent of the Display
Decimal Point position. A band setting of ‘0’ keeps the filter permanently
engaged at the filter level selected above.
7
SCALING STYLE
StYLE ? KEy          APLY
? KEy
If Input Values and corresponding Display Values are known, the Key-in
( KEY ) scaling style can be used. This allows scaling without the presence or
changing of the input signal. If Input Values have to be derived from the actual
input signal source or simulator, the Apply ( APLY ) scaling style must be used.
INPUT VALUE FOR SCALING POINT 1
INP 1 ? 0 to 29999
? 0.00
For Key-in ( KEY ) style, enter the first Input Value using the front panel buttons.
(The Input Range selection sets the decimal location for the Input Value).
For Apply ( APLY ) style, the meter shows the previously stored Input Value. To
retain this value, press the SEL button to advance to the next parameter. To
change the Input Value, press the RST button and apply the input signal to the
meter. Adjust the signal source externally until the desired Input Value appears.
Press the SEL button to enter the value being displayed.
DISPLAY VALUE FOR SCALING POINT 1
dSP 1 ? -19999 to 99999
? 0.00
Enter the first Display Value by using the front panel buttons. This is the same
for KEY and APLY scaling styles. The decimal point follows the dECPt selection.
INPUT VALUE FOR SCALING POINT 2
INP 2 ? 0 to 29999
? 100.00
For Key-in ( KEY ) style, enter the known second Input Value using the front
panel buttons.
For Apply ( APLY ) style, the meter shows the previously stored Input Value for
Scaling Point 2. To retain this value, press the SEL button to advance to the next
parameter. To change the Input Value, press the RST button and apply the input
signal to the meter. Adjust the signal source externally until the desired Input
Value appears. Press the SEL button to enter the value being displayed.
DISPLAY VALUE FOR SCALING POINT 2
dSP 2 ? -19999 to 99999
? 100.00
Enter the second Display Value by using the front panel buttons. This is the
same for KEY and APLY scaling styles.
General Notes on Scaling
1. When using the Apply ( APLY ) scaling style, input values for scaling points
must be confined to the signal input imits of the selected range.
2. The same Input Value should not correspond to more than one Display Value.
(Example: 10 V can not equal 0 and 10.)
3. For input levels beyond the programmed Input Values, the meter extends the
Display Value by calculating the slope from the two coordinate pairs ( INP1 /
dSP1 & INP2 / dSP2 ).
相关PDF资料
PDF描述
CUR-3285-MB BOX ABS 8.25X5.15X3.13" BLACK
CUR-3286-MB BOX ABS 10.15X6.15X3.13" BLACK
CUR-793-MB BOX ABS 4.1" X 2.23" X 2" W/BKTS
CUSTOM BGA CUSTOM BGA SOCKETS
CW2500 EPOXY OVERCOAT 0.26OZ
相关代理商/技术参数
参数描述
CUB70000 功能描述:COUNTER 8-DIGIT REFLECTIVE DISP RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB70010 功能描述:COUNTER 8-DIGIT YEL/GRN BACKLIT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB70020 功能描述:COUNTER 8-DIGIT RED BACKLIGHT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB7CCG0 功能描述:COUNTER 8-DIGIT LV GREEN RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB7CCR0 功能描述:COUNTER 8-DIGIT LV RED BACKLIGHT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮