参数资料
型号: EBCC024
文件页数: 2/2页
文件大小: 57K
代理商: EBCC024
2
Specifications are subject to change without notice (26.10.99)
Supply Specifications
Power supply AC types
Overvoltage cat. III (IEC 664)
Rated operational voltage
(IEC 38)
Through term. A1 & A2 024
24 VAC, -10/+15%
115
115 VAC, -10/+15%
230
230 VAC, -10/+15%
Frequency
50/60 Hz, -5/+5 Hz
Voltage interruption
≤ 40 ms
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand
voltage
4 kV (1.2/50 s)
Power supply DC types
Rated operational voltage
724
24 VDC, ±15%, A1 positive
Frequency
50/60 Hz, -5/+5 Hz
Dielectric voltage
None
Rated impulse withstand
voltage
800 V (1.2/50 s)
Rated operational current
AC
1,5 VA @ 230 VAC
1,5 VA @ 115 VAC
80 mA @ 24 VAC
DC
60 mA @ 24 VDC
General Specifications
EMC
Electromagnetic
Compatibility
Immunity
Acc. to IEC 801-4
Acc. to IEC 801-5
Power ON delay
≤ 200 ms
Power OFF delay
≥ 200 ms
Indication for
Power supply ON
LED, green
Output ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3
Operating temperature
-20° to +50°C (-4° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Weight
AC types
140 g
DC types
100 g
Screw terminals
Tightening torque
Max. 0.5 Nm acc. to IEC 947
Approvals
UL, CSA
EBC
Mode of Operation
Example 1
Aut. start with relay ON
The relay operates and the time
period starts when power sup-
ply is applied.
If an input pulse is received
before the end of the set time
period, the relay continues
Example 2
Start with relay OFF
The relay operates and the
time period starts at the lea-
ding edge of the first input
pulse.
If a new input pulse is received
before the end of the set time
operating for a full new time
period starting at the leading
edge of the input pulse.
If the set time period expires
before a new input pulse is
received, the relay releases.
period, the relay continues
operating for a full new time
period starting at the leading
edge of the new input pulse.
If the time expires before a
new input pulse is received,
the relay releases.
Operation Diagram
Power supply
Y1-Y2/Y1-B1
Relay ON (example 1)
Relay ON (example 2)
Wiring Diagram
Aut. start
L
Time Setting
Selection of time ranges
Upper knob:
3-position rotary switch.
Time setting
Lower knob:
Knob-adjustable on relative
scale 1-10.
(PE)
N
相关PDF资料
PDF描述
EBCC115
EBCC230
EBCC724
EC2C01C
ECG3300 TRANSISTOR | IGBT | N-CHAN | 400V V(BR)CES | 10A I(C) | SOT-186
相关代理商/技术参数
参数描述
EBCC115 制造商:未知厂家 制造商全称:未知厂家 功能描述:
EBCC230 制造商:未知厂家 制造商全称:未知厂家 功能描述:
EBCC724 制造商:未知厂家 制造商全称:未知厂家 功能描述:
EB-CC-CAP-L1 制造商:Molex 功能描述:RJLNXX MALE CAP WITH LANYARD
EB-CR10 制造商:Panasonic Industrial Company 功能描述:CHARGER