参数资料
型号: ELS-2-C-H
厂商: Curtis Industries
文件页数: 8/11页
文件大小: 0K
描述: LIQUID LEVEL CONTROL 240VAC
标准包装: 1
系列: ELS
类型: 电平控制 - 板
应用: 充水和排水控制
安装类型: 面板安装
电源电压: 120/240 VAC
其它名称: Q3843720
Curtis liquid level controls
?
Models DLC
Dual-level control with
lockout feature
Features
s Ideal for Pump and Heater Applications Requiring Lockout in the
Event of Loss of Water or Product Being Controlled
s Circuit Design Limits Short Circuit Probe Current to 10MA/24VAC
s Three-Probe Circuit Eliminates “Hunting” or Relay Chatter
s Built-in Holding Circuit for Differential Levels or Manual Reset
s Has Provision for Priming Switch for Applications Requiring Manual
Priming of System
s Solid-State Amplifier with SCR and Control Relay
s Sensitivity to 100,000 ohms
Specifications
Model Input Supply
Input Supply :
DLC-1 120VAC, 50/60 Hz
Maximum Signal or Probe Current : 10MA
DLC-2 240VAC, 50/60 Hz
DLC-3 24VAC, 50/60 Hz.
Maximum Allowable Supply Voltage Variation : ± 10%
Maximum Power Consumption : 3 Watts
Sensitivity Range : External circuit sensitivity fixed at 100,000 ohms; Lockout circuit
sensitivity fixed at 15,000 ohms
Operating Point Differential : 3% (Typical)
Maximum Signal or Probe Voltage : 24VAC
Outline and Mounting Dimensions
Control Relay : Plug-in types with dust cover
Probe Contacts : Internally connected for holding circuit
Load Contacts : 1/6 HP, 10 amp, Non-inductive/120VAC, 1/3 HP at 240VAC
One side of No. 1 relay actuates fill water solenoid valve, a second set of contacts
function as an internally connected holding circuit. One side of No. 2 relay is used
to operate a heater load contactor.
Ambient Operating Temperature : +32° F to +140° F
Standard Termination : .250” quick-connects
Description and Special Notes
The DLC control maintains liquids between a low and a high level. Activating the main switch on this dual-
relay unit pulls in control relay No. 1 and starts filling boiler tank through the solenoid valve. When liquid rises
to “XL”, minimum level, lockout control relay No. 2 energizes to operate the pump, heater core or contactor.
The solenoid valve continues to fill the tank until liquid reaches the “H” probe. When the liquid drops below the
“L” probe, the solenoid fill valve is again activated. Relay No. 2, he lockout control, remains energized as long
as liquid level remains above “XL” minimum level.
Ordering
Information
Typical Curtis Model Number
Model (Also refer to “Specifications” above)
DLC-1 - -
Contactor (add “C” if desired)
Enclosure – specify only if necessary –
N3-NEMA 3, N3C–NEMA 3/
Contactor, N4 – NEMA 4 JIC
The composite number above reads as a “DLC amplifier for 120VAC supply, without enclosure and without contactor.
Unless otherwise noted, when a contactor is ordered for the DLC unit, it is wired into the output of the No. 2 (heater control) relay. Contactors may be wired into the output of the No. 1
(solenoid valve control) relay or both No. 1 and No. 2 relays, as application may require. Specify with order. Refer to “Control Accessories,” page 7, for additional information.
For further information on catalog listed controls contact your area Curtis representative or Curtis distributor.
For custom design or modification contact your area Curtis representative or the factory direct.
10
相关PDF资料
PDF描述
ET-MX36-1 EXTRACTION TOOL MX36 SERIES
F16-2250 TRANSFORMER 8V 4.5A SNGL PRIMARY
F1891RD1600 MODULE DIODE 90A 600VAC
F1892D1600 MODULE DIODE 90A 600VAC
F7-24 XFRMR PWR 24.0VCT 2.4A .187
相关代理商/技术参数
参数描述
ELS308SDRDB/S530-A3/L18 制造商:Everlight Electronics Co 功能描述:
ELS-315SURWA 制造商:EVERLIGHT 制造商全称:Everlight Electronics Co., Ltd 功能描述:0.36 Single Digit Displays
ELS-315SURWA/S530-A3 制造商:Everlight Electronics Co 功能描述:SIGLE DIGIT DISPLAY HYPER-RED ALLNGAP - Rail/Tube
ELS-315SURWA-S530-A3 制造商:EVERLIGHT 制造商全称:Everlight Electronics Co., Ltd 功能描述:0.36 Single Digit Displays
ELS-315SYGWA 制造商:EVERLIGHT 制造商全称:Everlight Electronics Co., Ltd 功能描述:0.36 Single Digit Displays