参数资料
型号: G3NA-440B-AC100-240
厂商: Omron Electronics Inc-IA Div
文件页数: 15/18页
文件大小: 0K
描述: RELAY SSR 40A 230VAC
其它有关文件: SSR Design Considerations
产品目录绘图: G3NA Series
标准包装: 1
系列: G3NA
电路: SPST-NO(1 Form A)
输出类型: AC,过零
负载电流: 40A
输入电压: 100 ~ 240VAC
电压 - 负载: 180 ~ 528 V
安装类型: 底座安装或面板安装
端接类型: 螺丝端子
封装/外壳: Hockey Puck
包装: 散装
继电器类型: 继电器
产品目录页面: 2638 (CN2011-ZH PDF)
相关产品: Z2251-ND - MOUNTING PLATE ONE TOUCH G3NA
Y92B-A250-ND - HEATSINK SSR FOR G3NA SERIES
Z2000-ND - MOUNTING BRACKET FOR G3NA RELAY
其它名称: G3NA-440BAC100240
G3NA-440BAC100240-ND
G3NA440BAC100240
Z2587
Preventing Overheating with a
High-capacity Heat Sink (Y92B-P250NF)
? When the High-capacity Heat Sink is used, high-capacity switching
at 75 A or 90 A requires forced cooling with a fan. Connect the Fan
to a power supply according to its ratings specifications.
? If the Fan stops due to a power supply error, due to foreign matter
in the power supply connection, or due to aging, the Heat Sink will
heat to high temperatures, possibly resulting in failure of the SSR or
adverse affects on other devices. Implement an overheating pre-
vention measure, such as turning OFF the load current, if the Heat
Sink overheats.
? A thermostat is provided to detect overheating. The thermostat uses a
NC contact, i.e., the circuit will be opened for overheating. This thermo-
stat can be used to stop the operation of the SSR. Implement an over-
heating prevention measure by using this signal to output an alarm or
perform another response applicable to the system. Also, confirm that
there is no problem with the overall system.
? Do not connect the thermostat directly to the load power supply.
Connect it to a contactor or other shutoff device connected above
the SSR.
? Terminals equivalent to Faston #187 are used for the thermostat
terminals.
? Do not place heat-dissipating silicon grease on the thermostat.
? Do not solder the thermostat terminals.
? The following diagram shows a protective circuit example.
Circ u it breaker
2. DC-switching models
Less than 3 m
Load
Input G3 N A-UTU Output
? The input cable must be less than 3 m.
Loss Time
The loss time will increase when the G3NA is used at a low applied
voltage or current. Be sure that this does not cause any problems.
Loss time
Using DC Loads
For a DC or L load, a diode should be connected in parallel the load
to absorb the counter electromotive force of the load.
Coil
Circ u it breaker
(coil side)
Thermostat
(NC contact)
Y92B-P250NF
Load
(contact side)
Inp u t
SSR
Load
Load po w er
s u pply
po w er
s u pply
G3NA
Load side
Inp u t side
Ventilating a High-capacity Heat Sink
(Y92B-P250NF)
Circ u it
breaker
Fuses
Connect a quick-break fuse in series with the load as a short-circuit
protection measure. Use one of the fuses in the following table or one
with equivalent or better characteristics.
Recommended Fuses
60LFF8
G3NA-210B
? Refer to Ventilation Outside the Control Panel .
Operating Conditions
? Do not apply currents exceeding the rated current otherwise, the
temperature of the G3NA may rise excessively.
? As protection against accidents due to short-circuiting, be sure to
G3NA rated
load current
5A
8A
10 A
Fuse model Manufacturer Applicable SSR
60LFF5 Hinode Electric G3NA-205B
Co., LTD.
60LFF10
install protective devices, such as fuses and no-fuse breakers, on
the power supply side.
? Do not apply overvoltages to the input circuit or output circuit. Fail-
ure or burning may result.
? Do not drop the G3NA or otherwise subject it to abnormal shock.
Malfunction or failure may result.
? Keep the cooling system running continuously during the ON/OFF
operation of the SSR. This is to allow residual heat to dissipate
while the SSR is OFF. (load current 75A, 90A models)
EMC Directive Compliance (For -UTU type)
EMC directives can be complied with under the following conditions.
1. AC-switching models
? A capacitor must be connected to the input power supply.
15 A
20 A
25 A
30 A
40 A
45 A
50 A
75 A
80 A
100 A
60LFF15
60LFF20
50SHA20
60PFF25
50SHA25
60PFF30
50SHA30
50SHA40
50SHA45
50SHA50
50SHA75
50SHA80
50SHB100
G3NA-220B
G3NA-240B
G3NA-275B-UTU-2
G3NA-290B-UTU-2
? A capacitor, varistor and toroidal core must be connected to the
load power supply.
? The input cable must be less than 3 m.
Troidal core
Load
Reverse Connection
The output terminal side of the G3NA-D210B is connected to a built-
in diode to protect the SSR from damage that may result from
reverse connection. The SSR, however, cannot withstand one minute
or more if the wires are connected in reverse. Therefore, pay the
Input
G3 N A
Output
utmost attention not to make polarity mistakes on the load side.
3 m max.
Recommended Capacitor : 0.05 μ F, 500 V AC (Load)
0.1 μ F, 250 V AC (Input)
Recommended V aristor : 470 V , 1750 A
Recommended Troidal core : N EC/TOKI N :ESD-R-25B or equi v alent
Solid State Relay
G3NA
483
相关PDF资料
PDF描述
DRA3R48C2 RELAY CONTACT 3PH REV 480VAC 2A
DRA3R48B2 RELAY CONTACT 3PH REV 480VAC 2A
12X12-6-467MP TAPE TRANSFER ADHESIVE 12X12"
CA8B2,BK BOX 3.32X1.87X1.0" W/2 BTNS BLK
DRA3R48A2 RELAY CONTACT 3PH REV 480VAC 2A
相关代理商/技术参数
参数描述
G3NA440BDC524 制造商:Omron Electronic Components LLC 功能描述:Relay SSR 5mA 32V DC-IN 40A 528V AC-OUT 4-Pin 制造商:OMRON AUTOMATION AND SAFETY 功能描述:RELAY SSR 40A 5VDC 制造商:OMRON INDUSTRIAL AUTOMATION 功能描述:Relay SSR 5mA 32V DC-IN 40A 528V AC-OUT 4-Pin
G3NA-440B-DC5-24 功能描述:固态继电器-工业安装 SOLID STATE RELAY PHOTOCOUPLER RoHS:否 制造商:Crydom 控制电压范围:4 VDC to 32 VDC 负载电压额定值:7 VDC to 72 VDC 负载电流额定值:160 A 触点形式: 输出设备:SSR 安装风格:Panel
G3NA-450B 制造商:OMRON 制造商全称:Omron Electronics LLC 功能描述:Solid State Relay
G3NA-450B DC5-24 功能描述:固态继电器-工业安装 SOLID STATE RELAY PHOTOCOUPLER RoHS:否 制造商:Crydom 控制电压范围:4 VDC to 32 VDC 负载电压额定值:7 VDC to 72 VDC 负载电流额定值:160 A 触点形式: 输出设备:SSR 安装风格:Panel
G3NA-450B-2 DC5-24 功能描述:RELAY SSR 50A 5-24VDC ZERO CROSS RoHS:是 类别:继电器 >> 固态 系列:G3NA 其它有关文件:Declaration of Conformity 标准包装:20 系列:GN 电路:SPST-NO(1 Form A) 输出类型:AC,过零 导通状态电阻:- 负载电流:100A 输入电压:90 ~ 280VAC 电压 - 负载:24 ~ 280 V 安装类型:底座安装或面板安装 端接类型:螺丝端子 封装/外壳:Hockey Puck 供应商设备封装:- 包装:散装 继电器类型:继电器 相关产品:CC1172-ND - FILTER EMI FOR SINGLE PHASE SSR