参数资料
型号: GPC40-3.3
厂商: SL Power Electronics Manufacture of Condor/Ault Brands
文件页数: 1/2页
文件大小: 0K
描述: POWER SUPPLY SWITCHER 40W 3.3V
标准包装: 20
系列: GPC40
类型: 标准产品
输出数: 1
输出电压: 3.3V
输入电压: 85 ~ 264VAC
输出 - 1 @ 电流(最大): 3.3 VDC @ 8A
功率(瓦特): 40W
电源类型: 开关(开放框架)
应用: 商用
安装类型: 底座安装
尺寸/尺寸: 5.00" L x 3.00" W x 1.28" H(127.0mm x 76.2mm x 32.5mm)
工作温度: 0°C ~ 50°C
效率: 70%
电源(瓦特)- 最大: 40W
批准: CE,CSA,EN,TUV,UL
线路调节: 2%
负载调整: 2%
GPC40 Commercial/GPM40 Medical
40 WATT GLOBAL PERFORMANCE SWITCHERS
GLOBAL PERFORMANCE SWITCHERS
Summary:
? Wide-range ac input 85-264 Vac
? 2-year warranty
? Conducted EMI exceeds FCC Class B and CISPR 22
Class B (Commercial models) and CISPR 11
Class B (Medical models)
? Single and multiple outputs
? Commercial Approved to UL1950,
EN60950 E3:2000 and CSA-C22.2 No. 234
? Medical Approved to UL2601-1, EN60601-1 and
CSA22.2 No. 601
? Single and multiple outputs
? RoHS compliant models available (G suffix)
DC Power Supplies
?
marked to LVD
SPECIFICATIONS
Ac Input
85-264 Vac, 47-63 Hz single phase.
Input Current
Maximum input current at 120 Vac, 60 Hz with full rated output load: 1.3 A
Hold-Up Time
20 ms minimum from loss of ac input at full load, nominal line (115 Vac).
Output Power
40 W continuous, 50 W peak. Peak ratings are for 60 s maximum duration,
10% duty cycle. During peak load condition, output regulation may exceed
total regulation limits.
Overload Protection
Fully protected against short circuit and output overload.
Short circuit protection is cycling type power limit on outputs 1 & 2; foldback
type on output 3. Recovery after fault is automatic. See output ratings chart
for additional notes or conditions.
Overvoltage Protection.
Main outputs: 124% ± 12%.
Efficiency
70% at full rated load, nominal input voltage, depending on model and load
distribution.
Turn-on Time
Less than 1 second at 120 Vac, 25°C (inversely proportional to input voltage
and thermistor temperature).
Input Protection
Internal ac fuse provided. Designed to blow only if a catastrophic failure oc-
curs in the unit.
Inrush Current
Inrush is limited by internal thermistors. Inrush at 240 Vac under cold start
conditions will not exceed 34 A.
Temperature Coefficient
0.03%/°C typical on all outputs.
Environmental
Designed for 0 to 50°C operation at full rated output power; derate output
current and total output power by 2.5% per °C above 50°C.
Output Noise
0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential mode. Measured with noise
probe directly across output terminals of the power supply.
Transient Response
Main output—500 μs typical response time for return to within 0.5% of final value
for a 50% load step change. ?i/ ?t<0.2 A/μs. Maximum voltage deviation is 3.5%.
Startup/ shutdown overshoot less than 3%.
Remote Sense
Provided as a standard feature on single-output models.
Voltage Adjustment
Built-in potentiometer adjusts main output voltage ±5%.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the
following emissions requirements:
EMI SPECIFICATIONS COMPLIANCE LEVEL
Conducted Emissions EN55022 Class B; FCC Class B
Conducted Emissions EN55011 Class B; FCC Class B
Static Discharge EN61000-4-2, 6 kV contact, 8 kV air
RF Field Susceptibility EN61000-4-3, 3 V/meter
Fast Transients/Bursts EN61000-4-4, 2 kV, 5 kH
Surge Susceptibility EN61000-4-5, 1 kV diff., 2 kV com.
Line Frequency Harmonics EN61000-3-2
Commercial Safety
Approved to UL1950, CSA22.2 No. 950, IEC950, EN60950. All dc outputs are SELV
under normal and single fault conditions.
Medical Leakage Current
The maximum leakage current is as follows:
Test Condition Normal Single Fault
120 Vac @ 60 Hz input 25 μA 35 μA
264 Vac @ 60 Hz input 40 μA 60 μA
Medical Safety
Approved to UL2601-1, CSA22.2 No. 601 Level 3 and EN60601-1. UL file E116994;
CSA #LR46516. The output(s) are intended for safety earthed Signal Output
and Intermediate Circuits only. The output(s) are not acceptable for patient con-
nection without additional isolation. All dc outputs are SELV under normal and
single fault conditions.
All specifications are typical at nominal input, full load at 25 O C unless otherwise stated
相关PDF资料
PDF描述
T95V475K016HSSL CAP TANT 4.7UF 16V 10% 1410
GPC40-24 POWER SUPPLY SWITCHER 40W 24V
T95V335M020HSSL CAP TANT 3.3UF 20V 20% 1410
ABLS-7.3728MHZ-L4Q-T CRYSTAL 7.372800 MHZ 18PF SMD
GPC40-12 POWER SUPPLY SWITCHER 40W 12V
相关代理商/技术参数
参数描述
GPC40-48 制造商:SL Power Electronics 功能描述:- Bulk
GPC40-48G 功能描述:POWER SUPPLY SWITCHER 40W 48V RoHS:是 类别:电源 - 外部/内部(非板载) >> AC DC 转换器 系列:GPC40 产品培训模块:MP Modular-Configurable AC-DC Power Supply 特色产品:Configurable Power Supplies 标准包装:1 系列:MP
GPC40-5 功能描述:线性和开关式电源 40W 5V @ 8A RoHS:否 制造商:TDK-Lambda 产品:Switching Supplies 开放式框架/封闭式:Enclosed 输出功率额定值:800 W 输入电压:85 VAC to 265 VAC 输出端数量:1 输出电压(通道 1):20 V 输出电流(通道 1):40 A 商用/医用: 输出电压(通道 2): 输出电流(通道 2): 安装风格:Rack 长度: 宽度: 高度:
GPC40-5G 功能描述:线性和开关式电源 40W 5V @ 8A RoHS:否 制造商:TDK-Lambda 产品:Switching Supplies 开放式框架/封闭式:Enclosed 输出功率额定值:800 W 输入电压:85 VAC to 265 VAC 输出端数量:1 输出电压(通道 1):20 V 输出电流(通道 1):40 A 商用/医用: 输出电压(通道 2): 输出电流(通道 2): 安装风格:Rack 长度: 宽度: 高度:
GPC40-9 功能描述:线性和开关式电源 40W 9V @ 4.5A RoHS:否 制造商:TDK-Lambda 产品:Switching Supplies 开放式框架/封闭式:Enclosed 输出功率额定值:800 W 输入电压:85 VAC to 265 VAC 输出端数量:1 输出电压(通道 1):20 V 输出电流(通道 1):40 A 商用/医用: 输出电压(通道 2): 输出电流(通道 2): 安装风格:Rack 长度: 宽度: 高度: