PHASE-OUT
Power entry modules with line filter
GRM4
EMC products
"Lock and shield" mounting, line switch, fuseh. 5x20 mm with/without voltage sel. (series-parallel)
Snap-In Version
GRM4: with shield and line filter
Standard- or Medical-Filter
C14
70° C
Description
-PanelMount:
Snap-InVersionfromrear-side
-5Functions:
InletProtectionclassI,Lineswitch2-pole,withorwithoutFuseholder
forfuse-links5x20mm,withorwithoutvoltageselector,Linefilterin
standardandmedicalversion
-Onphase-out,notrecommendedfornewdesign
Approvals
-VDELicenseNumber:118913
-ULLicenseNumber:E72928
-CSALicenseNumber:701867
Characteristics
-Ultra-compactdesign
Timesaving"LockandShield"snap-indesignforrear-panelmounting
-Allsingleelementsarealreadywired
-Fuseholderontheinsideoftheequipmentpreventsaccidentaluseof
incorrectfuse-linksbytheuser
-Voltageselectorfortwovoltageranges
InnovativeEMC-shieldingwithflexiblesteelsegmentsforanexcellent
contacttothepanel
-Insulationcoverontherear-side
-QualifiedforuseinequipmentaccordingIEC/EN60950
Other versions on request
-Panelthickness1.0/2/2.5mm(max.)
-Fuseholder1-pole
-Lineswitch1-pole
-Voltageselectorwithothermarking
References
Weblinks
Technical Data
RatingsIEC
0.5-10A@Ta40°C/250VAC;50Hz
RatingsUL/CSA
0.5-10A@Ta40°C/125VAC;60Hz
LeakageCurrent
standard<0.5mA(250V/60Hz)
medical<5A(250V/60Hz)
DielectricStrength
>1.7kVDCbetweenL-N
>2.7kVDCbetweenL/N-PE
Testvoltage(2sec)
AllowableOperationTemp.
-25°Cto85°C
ClimaticCategory
25/085/21acc.toIEC60068-1
DegreeofProtection
fromfrontsideIP40acc.toIEC60529
ProtectionClass
Suitableforapplianceswithprotection
classIacc.toIEC61140
Terminal
Quickconnectterminals4.8x0.8mm
Solderterminalonrequest
Solderterminalsforvoltageselector
PanelThicknesss
Snap-in:1.5mm
(otheronrequest)
Material:Housing
Thermoplastic,black,UL94V-0
Appliance-Inlet/-Outlet
C14acc.toIEC/EN60320-1,
UL498,CSAC22.2no.42(forcold
condition)pin-temperature70°C,10A,
ProtectionclassI
Fuseholder
1or2pole,ShocksafecategoryPC2
acc.toIEC60127-6,
forfuse-links5x20mm
RatedPowerAcceptance@
Ta23°C
5x20:2W(1pole)/1.6W(2-pole)per
pole
PowerAcceptance@Ta>
23°C
Admissiblepoweracceptanceathig-
herambienttemperatureseederating
curves
LineSwitch
Rockerswitch2-pole,non-illuminated,
acc.toIEC61058-1
Voltageselector
optional,jumper,2digits
LineFilter
StandardandMedicalVersion,IEC
60939,IEC60601-1,UL1283,UL544,
EN133200,CSAC22.2no.8
MTBF
>1'400'000hacc.toMIL-HB-217F