参数资料
型号: TP15900-4
厂商: Cooper Bussmann
文件页数: 3/3页
文件大小: 0K
描述: SWITCH DISONNECT 50A 80V BLACK
标准包装: 21
系列: Telpower®
类型: 开关
电压: 80V
电流: 50A
Bussmann ?
Telpower ? Fused Disconnect Switch
DC Distribution/Protection System
TP15900-4
Proper sizing of the current limiting resistor, referred to
as R ALARM in the diagram below, is essential to prevent
excessive current, which could cause damage to the
LED in the disconnect head, from passing through the
remote alarm circuit. Because the LED is in series with
the remote alarm circuit, the maximum available alarm
circuit current should be limited to no more than 30 mA.
This is the maximum sustained current that can be toler-
ated by the LED. It is important to note that when calcu-
lating the size of the resistor, the number of circuits in
By calculating the minimum value of R ALARM as
described above, the maximum available remote alarm
circuit current will not exceed 30 mA. In the event of
multiple fuse blows, where the fuses are connected in
parallel on the same remote alarm bus, the total avail-
able remote alarm circuit current will be evenly divided
between each of the LED’s. For example, if three fuses
blow, each LED, indicating the presence of a blown fuse,
will conduct approximately 10 mA each, assuming the
total available remote alarm circuit current is 30mA.
parallel on the remote alarm circuit is irrelevant. The
resistor value should always be calculated assuming that
the total available alarm circuit current is conducted
through a single LED. This will insure that the 30 mA
limitation is not exceeded. The calculations required to
determine both the resistance and the wattage rating of
R ALARM are shown below .
METHOD FOR CALCULATING THE MINIMUM SERIES RESISTANCE VALUE NECESSARY TO LIMIT THE AVAIL-
ABLE ALARM CIRCUIT CURRENT TO ≤ 30mA. THE MINIMUM RESISTOR WATTAGE CALCULATIONS IS ALSO
SHOWN.
V SYSTEM
R ALARM =
I LED
(where I LED - 30 mA max.)
P RALARM = (V SYSTEM )(I LED ) (where I LED - 30 mA max).
Form No. TP15900-4
12-1-99
Page 3 of 3
SB99155
Rev. A
BIF Doc #5001
相关PDF资料
PDF描述
SQW-137-01-L-D CONN RCPT 2MM 74POS DL VERT PCB
4-103240-0-23 CONN HEADR BRKWAY .100 46POS STR
SQW-138-01-L-D CONN RCPT 2MM 76POS DL VERT PCB
SQW-139-01-L-D CONN RCPT 2MM 78POS DL VERT PCB
929836-08-27 CONN HEADER .100 DUAL STR 54POS
相关代理商/技术参数
参数描述
TP15900-41 功能描述:控制开关 - RoHS:否 制造商:Omron Industrial 控制类型:Emergency Stop 触点额定值:5 A at 125 VAC 触点形式:1 Form B (SPST-NC) 电压额定值: 电流额定值: 执行器:Pushbutton 照明:N 安装风格:
TP15900-41-2 功能描述:控制开关 4 POLE D.C. DISTR MODULE RoHS:否 制造商:Omron Industrial 控制类型:Emergency Stop 触点额定值:5 A at 125 VAC 触点形式:1 Form B (SPST-NC) 电压额定值: 电流额定值: 执行器:Pushbutton 照明:N 安装风格:
TP15900-41W 功能描述:控制开关 - RoHS:否 制造商:Omron Industrial 控制类型:Emergency Stop 触点额定值:5 A at 125 VAC 触点形式:1 Form B (SPST-NC) 电压额定值: 电流额定值: 执行器:Pushbutton 照明:N 安装风格:
TP15900-4W 功能描述:控制开关 - RoHS:否 制造商:Omron Industrial 控制类型:Emergency Stop 触点额定值:5 A at 125 VAC 触点形式:1 Form B (SPST-NC) 电压额定值: 电流额定值: 执行器:Pushbutton 照明:N 安装风格:
TP15914 功能描述:控制开关 - RoHS:否 制造商:Omron Industrial 控制类型:Emergency Stop 触点额定值:5 A at 125 VAC 触点形式:1 Form B (SPST-NC) 电压额定值: 电流额定值: 执行器:Pushbutton 照明:N 安装风格: