6.4 MODULE 4 - S ETPOINT O UTPUT P ARAMETERS ( 4-SPt )
4-SPt
SEL
PARAMETER MENU
Backlight
Unit Only
Pro
SPSEL
Setpoint
Select
Act-n
Setpoint
Action
SPt-n
Setpoint
Value
HYS-n
Hysteresis
Value
tON-n
On Time
Delay
tOF-n
Off Time
Delay
rSt-n
Output Reset
Action
rEn-n
Output Reset
W/Display
Stb-n
Standby
Operation
ChC-n
Change Display
Color with
Reset
Output State
The Setpoint Output Parameters are only active when an optional output
module is installed in the meter.
SPt-n ?
? 10000
SETPOINT VALUE
-19999 to 99999
SETPOINT SELECT
Enter the desired setpoint value. The decimal point position for the setpoint
SPSEL
?
NO
SP-1
SP-2
and hysteresis values follow the selection set in Module 1.
?
NO
HYS-n ?
Enter  the  setpoint  (output)  to  be  programmed.  The n in  the  following
parameters will reflect the chosen setpoint number. After the chosen setpoint
is completely programmed, the display will return to SPSEL . Repeat steps for
each setpoint to be programmed. Select NO to exit the module. The number of
setpoints available is setpoint output card dependent.
HYSTERESIS VALUE
1 to 59999
? 2
Enter desired hysteresis value. See Setpoint Output Figures for visual
explanation of how setpoint output actions (balanced and unbalanced) are
affected by the hysteresis. When the setpoint is a control output, usually
Enb-2
?
?
NO
SETPOINT 2 ENABLE
YES NO
balanced hysteresis is used. For alarm applications, usually unbalanced
hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on
the low side for high acting setpoints and functions on the high side for low
acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay
Select YES to enable Setpoint 2 and access the setup parameters. If NO is
can be used to prevent false triggering during process transient events.
selected, the unit returns to SPSEL and setpoint 2 is disabled.
ON TIME DELAY
Act-n ?
? HI-Ub
SETPOINT ACTION
HI-bL LO-bL HI-Ub
LO-Ub
tON-n ? 0.0 to 599.9 seconds
? 0.0
Enter the time value in seconds that the output is delayed from turning on
Enter the action for the selected setpoint (output). See Setpoint Output
Figures for a visual detail of each action.
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
HI-bL
LO-bL
=
=
High Acting, with balanced hysteresis
Low Acting, with balanced hysteresis
OFF TIME DELAY
HI-Ub
LO-Ub
=
=
High Acting, with unbalanced hysteresis
Low Acting, with unbalanced hysteresis
tOF-n
?
?
0.0
0.0
to
599.9 seconds
Enter the time value in seconds that the output is delayed from turning off
SP + ?Hys
SP + ?Hys
after the trigger point is reached. A value of 0.0 allows the meter to update the
SP
Hys
SP
Hys
output status per the response time listed in the Specifications.
SP - ?Hys
SP - ?Hys
OUTPUT
OFF
ON
OFF
OUTPUT
OFF
ON
OFF
OUTPUT RESET ACTION
STATE
TRIGGER POINTS
High Acting (Balanced Hys) =
HI-bL
STATE
TRIGGER POINTS
Low Acting (Balanced Hys) =
LO-bL
rSt-n
?
?
Auto
Auto LAtCH L-dLY
Enter the reset action of the output. See figure for details.
SP - Hys
SP
Hys
SP + Hys
SP
Hys
Auto = Automatic action; This action allows the output to automatically reset off
at the trigger points per the Setpoint Action shown in Setpoint Output
Figures. The “on” output may be manually reset (off) immediately by the
front panel RST button or user input.The output remains off until the trigger
point is crossed again.
OUTPUT
STATE
OFF
ON
OFF
OUTPUT
STATE
OFF
ON
OFF
LAtCH = Latch with immediate reset action; This action latches the output on at
TRIGGER POINTS
TRIGGER POINTS
the trigger point per the Setpoint Action shown in Setpoint Output Figures.
High Acting (Unbalanced Hys) =
HI-Ub
Low Acting (Unbalanced Hys) =
LO-Ub
Latch means that the output can only be turned off by the front panel RST
10
相关PDF资料
PDF描述
CUB5PB00 PROCESS METER RED/GREEN BKLT
CUB5RTR0 RTD METER REFLECTIVE
CUB5TCB0 METER PANEL LCD THERMOCOUPLE RED
CUB5USB0 USB OPTION CARD
CUB5VR00 METER LCD DC VOLT 8DIGIT
相关代理商/技术参数
参数描述
CUB5IB00 CALIBRATED 制造商:Red Lion Controls 功能描述:DIGITAL PANEL METER MODEL CUB5 WITH CERTIFICATE OF CALIBRATION
CUB5IR00 功能描述:DC METER REFLECTIVE DISP RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5OEMS 制造商:Red Lion Controls 功能描述:PROGRAMMING KIT FOR SOFTWARE
CUB5PB00 功能描述:PROCESS METER RED/GREEN BKLT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5PR00 功能描述:PROCESS METER REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030