参数资料
型号: LNXC2000
厂商: Red Lion Controls
文件页数: 2/8页
文件大小: 0K
描述: COUNTER DUAL PRESET 115VAC
标准包装: 1
系列: LYNX - LNXCC
计数速率: 50Hz
数字/字母数: 6
输入类型: 开关外壳或晶体管开关
输出类型: 接收器,晶体管
电源电压: 115VAC
显示器类型: LCD
其它名称: Q4894760
SPECIFICATIONS (Cont’d)
6. MAXIMUM COUNT RATES :
High Frequency : For the single preset unit only - 15 KHz max. square wave
input for all electronic sensors, under all modes of operation. For dual
preset units, the following chart lists the count rates for all the possible
prescale values.
DUAL PRESET UNITS ONLY
Prescale Value Frequency
0.00001 to 1 12 KHz
1.00001 to 2 9 KHz
2.00001 to 3 7 KHz
3.00001 to 4 5.5 KHz
4.00001 to 5 4.5 KHz
5.00001 to 6 4 KHz
6.00001 to 7 3.5 KHz
7.00001 to 8 3 KHz
8.00001 to 9 3 KHz
9.00001 to 9.99999 2.5 KHz
Note: For prescale values greater than 7, the timed delay output is affected
by the count speed (rate).
Low Frequency : both single and dual preset units - 100 Hz for switch
contact closures. Note: These units will operate with VCM (E through H)
modules.
7. CONTROL INPUTS : Active low (V IL = 0.5 V max.), internally pulled up
to 5 VDC through a 10 K ? resistor (I SNK = 0.5 mA).
Remote Reset : Response time = 10 msec. A low will reset the unit and
deactivate outputs.
Program Disable : A low will inhibit the changing of presets, prescale, and
timed outputs, as well as testing outputs in self-test.
Up/Down Control: Response time = 150 μsec. A low will cause the unit to
count down. A high will cause the unit to count up.
8. OUTPUTS :
Solid-State : Current sinking NPN Open Collector Transistors.
I SNK = 100 mA max., V OH = 30 VDC max., V OL = 1 V @ 100 mA.
Relay : Form C contacts max. rating 5 amps @ 120/240 VAC, 28 VDC
(resistive load), 1/8 H.P. @ 120 VAC (inductive load). The operate time is
5 msec. nominal and the release time is 3 msec. nominal.
Relay Life Expectancy - 100,000 cycles at max. rating. (As load level
decreases, life expectancy increases.)
Programmable Timed Output : The timed output can be programmed from
0.01 sec. to 99.99 sec., ± 0.1% + 10 msec. The timed output is set for 0.1
sec. at the factory.
9. MEMORY RETENTION : Non-volatile E 2 PROM retains all programmed
information when power is removed or interrupted.
10. INPUT, POWER, AND OUTPUT CONNECTIONS : Removable
terminal blocks.
11. ENVIRONMENTAL CONDITIONS :
Operating Temperature : 0 to 50°C
Storage Temperature : -40 to 70°C
Operating and Storage Humidity : 85% max. relative humidity
(non-condensing) from 0°C to 50°C.
Altitude : Up to 2000 meters
2
12. CERTIFICATIONS AND COMPLIANCES :
SAFETY
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
Type 4X Enclosure rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY
Immunity to EN 50082-2
Electrostatic discharge EN 61000-4-2 Level 2; 4 Kv contact
Level 3; 8 Kv air
Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m
80 MHz - 1 GHz
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O 2
Level 3; 2 Kv power 1
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms 1
150 KHz - 80 MHz
Emissions to EN 50081-2
RF interference EN 55011 Enclosure class A
Power mains class A
Notes:
1. Power lines had an external EMI line filter (RLC #LFIL0000 or
equivalent) installed.
2. I/O cables routed in metal conduit connected to earth ground.
Refer to the EMC Installation Guidelines section of the bulletin for
additional information.
13. CONSTRUCTION : Black plastic front bezel with black plastic insert.
Front panel meets NEMA 4X/IP65 requirements for wash-down and dusty
environments, when properly installed. Installation Category II, Pollution
Degree 2. (Panel gasket, mounting clip, nut fasteners, and screws included
with unit.)
14. WEIGHT : 0.8 lbs (0.36 kg).
FRONT PANEL FUNCTION DESCRIPTION
The units employ eight front panel buttons for control and data entry. The
button functions are as described below:
RESET “R”: Resets the counter to either zero or preset, depending on the
mode of operation selected. For this button to operate, the enable/disable
reset switch at the rear of the unit must be set to the enable (EN.) position.
The reset button is also used in conjunction with the preset button(s), to view
and change the timed output value(s). When reset is activated, all processes
are stopped or interrupted (i.e. outputs turn off, display is reset, etc.). This is
the case under any mode of operation, in any data entry mode.
PRESET “P1” (“P2”): Labeled P1 and P2 (single preset units only have the
P1 preset button).
The preset 1 value is displayed when the P1 button is pressed, and the Preset
Value mode is accessed (See Program Preset Value). The value remains
displayed for approximately 10 seconds after the button is released. The
preset buttons are also used, in conjunction with the reset button, to view and
change the timed output values (See Program Timed Output Value section.)
ENTER “E”: Used when programming the Preset Value or the Timed Output
Value. After the desired value is obtained on the display, pressing the E
相关PDF资料
PDF描述
LP-56-850 XFRMR 115/230V 28V 1.7A 48VA PCB
LS412460 DIODE MOD ISO SGL 2400V 600A
M4L-3-10 XFRMR 115V 8.7A 1000VA
M5060TB800 MODULE POWER 60A 800V 3PH BRIDGE
M81969/14-06 TOOL EXTRACTION #8 CONTACT PLAST
相关代理商/技术参数
参数描述
LNXCC000 制造商:Red Lion Controls 功能描述:CONTACT INPUT COUNTER
LNXEK-GK-519 制造商:GHI electronics 功能描述:Interface Development Tools FEZ Lynx Expandable Kit - Gadgeteer
LNY152C01 制造商:Panasonic Industrial Company 功能描述:LCD
LNY153C01 制造商:Panasonic Industrial Company 功能描述:LCD
LNY153C02 制造商:Panasonic Industrial Company 功能描述:DISPLAY