MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
MAX16046 fig03
MAX16046 fig04
V CC
V CC
2V/div
0V
RESET
2V/div
0V
EN_OUT_
2V/div
0V
HIGH-Z
UVLO
ASSERTED
LOW
2V/div
0V
RESET
2V/div
0V
EN_OUT_
2V/div
0V
20ms/div
Figure 3. RESET and EN_OUT_ During Power-Up, EN_OUT_ Is
in Open-Drain Active-Low Configuration
Sequencing
Each EN_OUT_ has one or more associated MON_
inputs, facilitating the voltage monitoring of multiple
power supplies. To sequence a system of power sup-
plies safely, the output voltage of a power supply must
be good before the next power supply may turn on.
Connect EN_OUT_ outputs to the enable input of an
external power supply and connect MON_ inputs to the
output of the power supply for voltage monitoring. More
than one MON_ may be used if the power supply has
multiple outputs.
Sequence Order
The MAX16046/MAX16048 utilize a system of ordered
slots to sequence multiple power supplies. To deter-
mine the sequence order, assign each EN_OUT_ to a
slot ranging from Slot 0 to Slot 11. EN_OUT_(s)
assigned to Slot 0 are turned on first, followed by out-
puts assigned to Slot 1, and so on through Slot 11.
Multiple EN_OUT_s assigned to the same slot turn on at
the same time.
Each slot has a built-in configurable sequence delay
(registers r50h to r54h) ranging from 20 μs to 1.6s.
During a reverse sequence, slots are turned off in
reverse order starting from Slot 11. The MAX16046/
MAX16048 may be configured to power-down in simul-
taneous mode or in reverse sequence mode as set in
r54h[4]. See Tables 10, 11, and 12 for the EN_OUT_
slot assignment bits and Tables 13 and 14 for the
sequence delays.
Monitoring Inputs While Sequencing
An enabled MON_ input may be assigned to a slot rang-
ing from Slot 1 to Slot 12. Monitoring inputs are always
checked at the beginning of a slot. The inputs are given
the power-up fault delay within which they must satisfy
Maxim Integrated
10ms/div
Figure 4. RESET and EN_OUT_ During Power-Up, EN_OUT_ Is
in Push-Pull Active-High Configuration
the programmed undervoltage limit; otherwise a fault
condition will occur. The fault occurs regardless of the
critical fault enable bits. This undervoltage limit cannot
be disabled during power-up and power-down.
EN_OUT_s configured for open-drain, push-pull, or
charge-pump operation are always asserted at the end
of a slot, following the sequence delay. See Tables 10,
11, and 12 for the MON_ slot assignment bits.
Slot 0 does not monitor any MON_ input. Instead, Slot 0
waits for the Software Enable bit r4Dh[0] to be a logic
‘0 ’ and for the voltage on EN to rise above 0.525V
before asserting any assigned outputs. Outputs
assigned to Slot 0 are asserted before the Slot 0
sequence delay. Generally, Slot 0 controls the enable
inputs of power supplies that are first in the sequence.
Similarly, Slot 12 does not control any EN_OUT_ outputs.
Rather, Slot 12 monitors assigned MON_ inputs and then
enters the power-on state. Generally, Slot 12 monitors
the last power supplies in the sequence. The power-up
sequence is complete when any MON_ inputs assigned
to Slot 12 exceed their undervoltage thresholds and the
sequence delay is expired. If no MON_ inputs are
assigned to Slot 12, the power-up sequence is complete
after the slot sequence delay is expired.
The output rail(s) of a power supply should be monitored
by one or more MON_ inputs placed in the succeeding
slot, ensuring that the output of the supply is not checked
until it has first been turned on. For example, if a power
supply uses EN_OUT1 located in Slot 3 and has two
monitoring inputs, MON1 and MON2, they must both be
assigned to Slot 4. In this example, EN_OUT1 turns on at
the end of Slot 3. At the start of Slot 4, MON1 and MON2
must exceed the undervoltage threshold before the pro-
grammed power-up fault delay; otherwise a fault triggers.
29
相关PDF资料
PDF描述
MAX6440UTAIRD3+T IC BATTERY MON SNGL SOT23-6
MAX16048ETN+ IC EE-PROG SYS MGR 8CH 56-TQFN
ACC05DREF-S13 CONN EDGECARD 10POS .100 EYELET
MAX16062ATG+ IC SUPERVISOR OCT 1% 24TQFN-EP
CDPH4D19FNP-8R0MC INDUCTOR 8.0UH 0.9A SHIELD SMD
相关代理商/技术参数
参数描述
MAX16046ETN+ 功能描述:监控电路 12Ch EEPROM Prob System Manager RoHS:否 制造商:STMicroelectronics 监测电压数: 监测电压: 欠电压阈值: 过电压阈值: 输出类型:Active Low, Open Drain 人工复位:Resettable 监视器:No Watchdog 电池备用开关:No Backup 上电复位延迟(典型值):10 s 电源电压-最大:5.5 V 最大工作温度:+ 85 C 安装风格:SMD/SMT 封装 / 箱体:UDFN-6 封装:Reel
MAX16046ETN+CK4 功能描述:监控电路 12Ch EEPROM Prob System Manager RoHS:否 制造商:STMicroelectronics 监测电压数: 监测电压: 欠电压阈值: 过电压阈值: 输出类型:Active Low, Open Drain 人工复位:Resettable 监视器:No Watchdog 电池备用开关:No Backup 上电复位延迟(典型值):10 s 电源电压-最大:5.5 V 最大工作温度:+ 85 C 安装风格:SMD/SMT 封装 / 箱体:UDFN-6 封装:Reel
MAX16046ETN+CK9 功能描述:监控电路 12Ch EEPROM Prob System Manager RoHS:否 制造商:STMicroelectronics 监测电压数: 监测电压: 欠电压阈值: 过电压阈值: 输出类型:Active Low, Open Drain 人工复位:Resettable 监视器:No Watchdog 电池备用开关:No Backup 上电复位延迟(典型值):10 s 电源电压-最大:5.5 V 最大工作温度:+ 85 C 安装风格:SMD/SMT 封装 / 箱体:UDFN-6 封装:Reel
MAX16046ETN+T 功能描述:监控电路 12Ch EEPROM Prob System Manager RoHS:否 制造商:STMicroelectronics 监测电压数: 监测电压: 欠电压阈值: 过电压阈值: 输出类型:Active Low, Open Drain 人工复位:Resettable 监视器:No Watchdog 电池备用开关:No Backup 上电复位延迟(典型值):10 s 电源电压-最大:5.5 V 最大工作温度:+ 85 C 安装风格:SMD/SMT 封装 / 箱体:UDFN-6 封装:Reel
MAX16046EVKIT+ 功能描述:电源管理IC开发工具 MAX16046 Eval Kit RoHS:否 制造商:Maxim Integrated 产品:Evaluation Kits 类型:Battery Management 工具用于评估:MAX17710GB 输入电压: 输出电压:1.8 V