参数资料
型号: PAXLRT00
厂商: Red Lion Controls
文件页数: 5/8页
文件大小: 0K
描述: METER RTD TEMP 4-DIGIT
产品目录绘图: PAX Lite Series
PAX Lite Series Cut Out
标准包装: 1
系列: PAX®LITE
类型: RTD
显示器样式: 红色字符,黑色背景
显示器类型: LED
显示器正面尺寸: 3.80" L x 1.95" W(96.5 x 49.5mm)
显示器位数: 4
显示器位数 - 高度: 0.560"(14.22mm)
安装类型: 面板安装
端子: 端接块
电源电压: 85 ~ 250VAC
其它名称: RLC115
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro-
Magnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, source or coupling method into the meter may be different for various
installations. The meter becomes more immune to EMI with fewer I/O
connections. Cable length, routing, and shield termination are very important
and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the meter and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far as possible
from contactors, control relays, transformers, and other noisy components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC# FCOR0000)
TDK # ZCAT3035-1330A
Steward # 28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC# LFIL0000)
Schaffner # FN670-1.8/07
Corcom # 1 VR3
Note: Reference manufacturer ’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
3.0 R EVIEWING
THE
F RONT B UTTONS
AND
D ISPLAY
8.8.8.8 C
PAR
KEY
PAR
?
?
DISPLAY MODE OPERATION
Access Programming Mode or Display Input Reading
Display Peak (HI) Reading
Display Valley (LO) Reading
PROGRAMMING MODE OPERATION
Store selected parameter and index to next parameter
Increment value or change selection
Decrement value or change selection
PEAK/VALLEY DETECTION
The meter will automatically record the highest input reading (peak) and the
lowest input reading (valley) for later recall. These values are stored at power-
down to allow monitoring the process limits over any length of time (shifts, days,
etc.). A selectable capture delay time is used to prevent detection of false peak or
valley readings caused by sudden short spikes or unusual process events.
The peak and valley readings can be viewed and reset using the front panel
keys as described below.
View Peak, Valley and Input readings:
To view Peak, press ? . Meter displays ?? followed by the Peak reading.
To view Valley, press ? . Meter displays ?? followed by the Valley reading.
To view Input, press PAR . Meter displays ???? followed by the current
Input reading.
Note: The decimal point to the right of digit 1 flashes while the peak or valley
reading is displayed.
5
Reset Peak and/or Valley to the current Input reading:
To reset Peak and Valley, press ? and ? simultaneously.
To reset Peak only, press and hold ? then press PAR .
To reset Valley only, press and hold ? then press PAR .
In each case, the meter displays ???? followed by the current Input reading.
相关PDF资料
PDF描述
PAXLSG00 METER STRAIN GAGE 3 1/2-DIGIT
PAXLTC00 METER THERMOCOUPLE 4-DIGIT
PAXLVA00 VOLTMETER AC 3 1/2-DIGIT
PAXLVD00 VOLTMETER DC 3 1/2-DIGIT
PAXTM100 TIMER DISPLAY 1/8 DIN PRESET 6 D
相关代理商/技术参数
参数描述
PAXLSG00 功能描述:METER STRAIN GAGE 3 1/2-DIGIT RoHS:否 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXLT000 制造商:Red Lion Controls 功能描述:METER, TC/RTD TEMP WITH DUAL RELAY 制造商:Red Lion Controls 功能描述:TC/RTD TEMP WITH DUAL RELAY
PAXLT0U0 制造商:Red Lion Controls 功能描述:METER, UL LISTED TC/RTD TEMP W/ D RELAY 制造商:Red Lion Controls 功能描述:UL LISTED TC/RTD TEMP WITH DUAL
PAXLTC00 功能描述:METER THERMOCOUPLE 4-DIGIT RoHS:否 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXLVA00 功能描述:VOLTMETER AC 3 1/2-DIGIT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030