参数资料
型号: PAXLRT00
厂商: Red Lion Controls
文件页数: 7/8页
文件大小: 0K
描述: METER RTD TEMP 4-DIGIT
产品目录绘图: PAX Lite Series
PAX Lite Series Cut Out
标准包装: 1
系列: PAX®LITE
类型: RTD
显示器样式: 红色字符,黑色背景
显示器类型: LED
显示器正面尺寸: 3.80" L x 1.95" W(96.5 x 49.5mm)
显示器位数: 4
显示器位数 - 高度: 0.560"(14.22mm)
安装类型: 面板安装
端子: 端接块
电源电压: 85 ~ 250VAC
其它名称: RLC115
5.0 C ALIBRATING
CALIBRATION MODE
THE
M ETER
METER INPUT CALIBRATION
?
???? ?
??
? to ??
?
???? ?
??
To enter Calibration Mode, select ??? < > ??? at the end
of Programming Mode, and press the PAR key. In Calibration Mode, the user
can restore the meter to factory default settings or recalibrate the signal input if
necessary.
To prevent inadvertent entries, an access code must be entered to perform any
operation in Calibration Mode. Upon entering Calibration Mode, the meter
initially displays Code 50. Press the up or down arrow keys to select the access
code for the desired operation. If an access code other than those shown below
is entered, the meter exits Calibration Mode and returns to normal display mode.
The meter has been fully calibrated at the factory. If the meter appears to be
indicating incorrectly or inaccurately, refer to the troubleshooting section
before attempting this procedure. When re-calibration is required (generally
every 2 years) , the procedure should only be performed by qualified
technicians using appropriate equipment. Resistance source accuracies of
0.02% or better are required.
The procedure consists of applying accurate signal levels to the meter input
in a series of two steps. Allow a 30-minute warm-up period before starting
calibration. To begin the input calibration, enter access Code 48 and press the
PAR key .
?
???? ?
??
FACTORY SETTINGS
ENTER ZERO REFERENCE
Meter displays ?? . Apply 0 ohms to the meter input by shorting Terminals 4,
5, and 6. Allow the meter to stabilize at least 20 seconds after shorting the
terminals, and then press PAR .
The factory settings for the programming parameters are shown in the
previous section in the alternating display illustrations. All programming
parameters can be restored to the factory default settings by entering the access
Code 66 and pressing the PAR key. The meter briefly displays ???? and then
returns to Code 50. This procedure resets only parameters that are accessed
through Programming Mode. The Calibration Mode settings (input calibration
levels) are not affected.
APPLY PRECISION RESISTANCE
Meter displays ???? . Connect a precision 300 ohm resistor across Terminals
5 and 6. Terminals 4 and 5 remain shorted. (Note: Be certain to short Terminals
4 and 5 at the resistor as shown in the drawing below. Shorting terminals may
lead to incorrect calibration.)
4
5
6
Allow the meter to stabilize at least 20 seconds after making the connections,
and then press PAR . The meter briefly displays ??? and returns to the normal
display mode. Calibration is now complete. It is recommended to check
calibration by comparing the displayed temperature with a precision thermometer.
TROUBLESHOOTING
The majority of all problems with the meter can be traced to improper connections or improper programming set-ups. Be sure all connections are
clean and tight and check the programming set-ups for correct data.
For further technical assistance, contact technical support at the appropriate company numbers listed.
PROBLEM
NO DISPLAY
“ ???? ” IN DISPLAY
“ ?? ?? ?? ? ” or “ ??? ?? ?? ? ” IN DISPLAY
DISPLAY WANDERS
JITTERY DISPLAY
POSSIBLE CAUSE
1. Power off, improperly connected, or brown-out.
1. Program data error.
1. Input display out of range.
2. Loss of data set-ups.
1. Loss of data set-ups.
1. Electrical “Noise” in process or sensor lines.
2. Process inherently unstable.
REMEDIES
1a. Check wiring.
1b. Verify power.
1. Press PAR and check data set-ups.
1a. Change display resolution to “1” degree.
1b. Reduce offset value.
2a. Check data set-ups.
2b. Check for electrical disturbance.
2c. Disconnect and reconnect power.
1a. Check data set-ups.
1b. Disconnect and reconnect power.
1c. Check for electrical disturbance.
1a. Increase digital filtering.
1b. Re-route signal wires.
2. Dampen process to eliminate oscillations.
“ ???? ” IN DISPLAY
1.
2.
3.
4.
Probe unconnencted.
Broken or burnout probe.
Excessive probe temperature.
Input overload.
1.
2.
3.
4.
Connect probe.
Repair or obtain new probe.
Reduce temperature.
Check input levels.
“ ???? ” IN DISPLAY
1. Input shorted.
7
1. Check input connections.
相关PDF资料
PDF描述
PAXLSG00 METER STRAIN GAGE 3 1/2-DIGIT
PAXLTC00 METER THERMOCOUPLE 4-DIGIT
PAXLVA00 VOLTMETER AC 3 1/2-DIGIT
PAXLVD00 VOLTMETER DC 3 1/2-DIGIT
PAXTM100 TIMER DISPLAY 1/8 DIN PRESET 6 D
相关代理商/技术参数
参数描述
PAXLSG00 功能描述:METER STRAIN GAGE 3 1/2-DIGIT RoHS:否 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXLT000 制造商:Red Lion Controls 功能描述:METER, TC/RTD TEMP WITH DUAL RELAY 制造商:Red Lion Controls 功能描述:TC/RTD TEMP WITH DUAL RELAY
PAXLT0U0 制造商:Red Lion Controls 功能描述:METER, UL LISTED TC/RTD TEMP W/ D RELAY 制造商:Red Lion Controls 功能描述:UL LISTED TC/RTD TEMP WITH DUAL
PAXLTC00 功能描述:METER THERMOCOUPLE 4-DIGIT RoHS:否 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXLVA00 功能描述:VOLTMETER AC 3 1/2-DIGIT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030