参数资料
型号: Y92BA100
厂商: Omron Electronics Inc-IA Div
文件页数: 13/18页
文件大小: 0K
描述: HEAT SINK FOR 10A G3NA SERIES
产品目录绘图: Y92B Series Heat Sink
标准包装: 1
系列: G3NA
附件类型: 散热片
适用于相关产品: G3NA 系列
产品目录页面: 2638 (CN2011-ZH PDF)
配用: Z1237-ND - RELAY SSR 1A 24VDC SIP PC MNT
Z1236-ND - RELAY SSR 1A 12VDC SIP PC MNT
Z1235-ND - OUTPUT MODULE AC QC 15MA 5-24VDC
Z1234-ND - INPUT MODULE AC 15MA 4-32VDC
Z1047-ND - RELAY SSR SPST 150MA 6-SMT
Z1046-ND - RELAY SSR SPST 150MA 4-SMT
Z1045-ND - RELAY SSR SPST 150MA 6-DIP
Z1044-ND - RELAY SSR SPST 150MA 4-DIP
Z1043-ND - RELAY SSR DPST 120MA 8-SMT
Z1042-ND - RELAY SSR DPST 120MA 8-DIP
更多...
其它名称: Y92B-A100
Z927
Operating and Storage Locations
Relationship between SSRs and Duct Height
Do not use or store the G3NA in the following locations. Doing so
may result in damage, malfunction, or deterioration of performance
characteristics.
Incorrect Example
D u ct
Countermeasure 1
50 mm max.
(A height of no
more than half
Countermeasure 2
D u ct
the SSR's height
? Do not use or store in locations subject to direct sunlight.
? Do not use in locations subject to ambient temperatures outside
the range –20 to 60 ° C.
? Do not use in locations subject to relative humidity outside the
range 45% to 85% or locations subject to condensation as the
V ertical
direction
is recommended.)
Base
Airflo w
SSR
result of severe changes in temperature.
? Do not store in locations subject to ambient temperatures outside
the range –30 to 70 ° C.
D u ct
D u ct
D u ct
? Do not use or store in locations subject to corrosive or flammable
gases.
? Do not use or store in locations subject to dust (especially iron
dust) or salts.
? Do not use or store in locations subject to shock or vibration.
Do not s u rro u nd the SSR
w ith d u cts, other w ise the
heat radiation of the SSR
w ill b e ad v ersely affected.
Use short d u cts.
If the d u cts cannot b e
shortened, place the SSR on
a metal b ase so that it is not
s u rro u nded b y the d u cts.
? Do not use or store in locations subject to exposure to water, oil, or
chemicals.
? Do not use or store in locations subject to high temperatures or
high humidity.
? Do not use or store in locations subject to salt damage.
? Do not use or store in locations subject to rain or water drops.
■ Precautions for Correct Use
Please observe the following precautions to prevent failure to oper-
ate, malfunction, or undesirable effect on product performance.
Before Actual Operation
1. The G3NA in operation may cause an unexpected accident.
Therefore it is necessary to test the G3NA under the variety of
conditions that are possible. As for the characteristics of the
G3NA, it is necessary to consider differences in characteristics
between individual SSRs.
2. Unless otherwise specified, the ratings in this catalog are tested
values in a temperature range between 15 ° C and 30 ° C, a relative
humidity range between 25% and 85%, and an atmospheric pres-
sure range between 88 and 106 kPa (standard test conditions
according to JIS C5442). It will be necessary to provide the above
conditions as well as the load conditions if the user wants to con-
firm the ratings of specific G3NAs.
Mounting Method
SSR Mounting Pitch (Panel Mounting)
D u ct
Ventilation Outside the Control Panel
Be a w are of airflo w
D u ct
Ventilation
o u tlet
(axial fan)
Air inlet
If the air inlet or air outlet has a filter, clean the filter regularly to pre-
vent it from clogging to ensure an efficient flow of air.
Do not locate any objects around the air inlet or air outlet, otherwise
the objects may obstruct the proper ventilation of the control panel.
A heat exchanger, if used, should be located in front of the SSRs to
ensure the efficiency of the heat exchanger.
? Please reduce the ambient temperature of SSRs. The rated load
current of an SSR is measured at an ambient temperature of 40 ° C.
? An SSR uses a semiconductor in the output element. This causes
the temperature inside the control panel to increase due to heating
resulting from the passage of electrical current through the load. To
restrict heating, attach a fan to the ventilation outlet or air inlet of
the control panel to ventilate the panel. This will reduce the ambient
temperature of the SSRs and thus increase reliability. (Generally,
each 10 ° C reduction in temperature will double the expected life.)
Load current (A)
5A
10 A
20 A
40 A
75 A
90 A
60 mm min.
Required number
of fans per SSR
0.08
0.16
0.31
0.62
1.2
1.44
Example: For 10 SSRs with load currents of 10 A,
0.16 x 10 = 1.6
Vertical direction
Thus, 2 fans would be required.
80 mm min.
30 mm min.
Size of fans: 92 mm 2 , Air volume: 0.7 m 3 /min,
Ambient temperature of control panel: 30 ° C
If there are other instruments that generate heat in the control panel
other than SSRs, additional ventilation will be required.
Solid State Relay
G3NA
481
相关PDF资料
PDF描述
433115-13-0 TERM BARRIER 13CIRC 1 ROW .4375
433110-13-0 TERM BARRIER 13CIRC 1 ROW .4375
MP-101635-2.5-8A LABEL ID PRODUCT
MF-MSMF110/16-2 PTC RESETTABLE 1.10A 16V 1812
FOD410SDV TRIAC DRV ZC 300MA 600V VDE 6SMD
相关代理商/技术参数
参数描述
Y92B-A100 功能描述:散热片 STD MT HEAT SINK G3N RoHS:否 制造商:Ampro By ADLINK 产品:Heat Sink Accessories 安装风格:Through Hole 散热片材料: 散热片样式: 热阻: 长度: 宽度: 高度: 设计目的:Express-HRR
Y92BA150N 制造商:OMRON AUTOMATION AND SAFETY 功能描述:HEAT SINK FOR 25A G3NA SERIES 制造商:Omron Electronic Components LLC 功能描述:Heat Sink Passive 1.37|C/W 制造商:OMRON INDUSTRIAL AUTOMATION 功能描述:Heat Sink Passive 1.37°C/W
Y92B-A150N 功能描述:散热片 STD MT HEAT SINK G3N RoHS:否 制造商:Ampro By ADLINK 产品:Heat Sink Accessories 安装风格:Through Hole 散热片材料: 散热片样式: 热阻: 长度: 宽度: 高度: 设计目的:Express-HRR
Y92BA150NV 制造商:OMRON AUTOMATION AND SAFETY 功能描述:HEAT SINK FLUSH MOUNT FOR G3NA 制造商:OMRON INDUSTRIAL AUTOMATION 功能描述:HEAT SINK
Y92B-A150NV 功能描述:散热片 HEAT SINK RoHS:否 制造商:Ampro By ADLINK 产品:Heat Sink Accessories 安装风格:Through Hole 散热片材料: 散热片样式: 热阻: 长度: 宽度: 高度: 设计目的:Express-HRR