参数资料
型号: ADE7761BARSZ-RL
厂商: Analog Devices Inc
文件页数: 18/24页
文件大小: 0K
描述: IC ENERGY METERING 1PHASE 20SSOP
标准包装: 1,500
输入阻抗: 790 千欧
测量误差: 0.1%
电压 - 高输入/输出: 2.4V
电压 - 低输入/输出: 0.8V
电流 - 电源: 3.65mA
电源电压: 4.75 V ~ 5.25 V
测量仪表类型: 单相
工作温度: -40°C ~ 85°C
安装类型: 表面贴装
封装/外壳: 20-SSOP(0.209",5.30mm 宽)
供应商设备封装: 20-SSOP
包装: 带卷 (TR)
ADE7761B
Fault with Active Input Greater Than Inactive Input
If V 1A is the active current input (that is, being used for billing),
and the voltage signal on V 1B (inactive input) falls below 93.75%
of V 1A , the fault indicator becomes active. Both analog inputs
are filtered and averaged to prevent false triggering of this logic
output. As a consequence of the filtering, there is a time delay of
approximately 3 sec on the Logic Output FAULT after the fault
event. The FAULT logic output is independent of any activity on
the F1 or F2 outputs. Figure 28 shows one condition under
which FAULT becomes active. Because V 1A is the active input
and it is still greater than V 1B , billing is maintained on V 1A ; that
Calibration Concerns
Typically, when a meter is being calibrated, the voltage and current
circuits are separated, as shown in Figure 30. This means that
current passes through only the phase or neutral circuit. Figure 30
shows current being passed through the phase circuit. This is
the preferred option because the ADE7761B starts billing on the
input V 1A on power-up. The Phase Circuit CT is connected to
V 1A in Figure 30. Because there is no current in the neutral circuit,
the FAULT indicator comes on under these conditions. However,
this does not affect the accuracy of the calibration and can be
used as a means to test the functionality of the fault detection.
FILTER
V 1A V 1A
is, no swap to the V 1B input occurs. V 1A remains the active input.
FAULT
AND
IB
CT
R F
V 1A
V 1B
A
COMPARE
RB
V 1A
C F
0V
AGND
V 1A
V 1B
V 1N
B
TO
MULTIPLIER
TEST
IB
AGND
RB
0V
C F
V 1N
V 1B < 93.75% OF V 1A
FAULT
V 1B
CURRENT
RA 1
CT
R F
V 1B
RB 1
C F
<0 >0
ACTIVE POINT – INACTIVE INPUT
6.25% OF ACTIVE INPUT
Figure 28. Fault Conditions for Active Input Greater Than Inactive Input
V
240V rms
VR 1
R F
C T
V 2P
V 2N
Fault with Inactive Input Greater Than Active Input
Figure 29 illustrates another fault condition. If the difference
between V 1B , the inactive input, and V 1A , the active input (that
is, being used for billing), becomes greater than 6.25% of V 1B ,
the FAULT indicator becomes active and a swap over to the V 1B
input occurs. The Analog Input V 1B becomes the active input.
Again, a time constant of about 3 sec is associated with this swap.
V 1A does not swap back to the active channel until V 1A is greater
than V 1B , and the difference between V 1A and V 1B , in this order,
becomes greater than 6.25% of V 1A . However, the FAULT indi-
cator becomes inactive as soon as V 1A is within 6.25% of V 1B . This
threshold eliminates potential chatter between V 1A and V 1B .
1 RB + VR = RF.
Figure 30. Conditions for Calibration of Channel B
If the neutral circuit is chosen for the current circuit in the
arrangement shown in Figure 30, this may have implications for
the calibration accuracy. The ADE7761B powers up with the
V 1A input active as normal. However, because there is no current
in the phase circuit, the signal on V 1A is zero. This causes a fault
to be flagged and the active input to be swapped to V 1B (neutral).
The meter can be calibrated in this mode, but the phase and
neutral CTs may differ slightly. Because under no-fault conditions
all billing is carried out using the phase CT, the meter should be
calibrated using the phase circuit. Of course, both phase and
V 1A
V 1B
V 1A
A
FILTER
AND
COMPARE
FAULT
neutral circuits can be calibrated.
MISSING NEUTRAL MODE
0V
AGND
V 1A
V 1B
V 1N
B
TO
MULTIPLIER
The ADE7761B integrates a novel fault detection scheme that
warns and allows the ADE7761B to continue to bill in case a
meter is connected to only one wire (see Figure 31). For correct
V 1A < 93.75% OF V 1B
FAULT + SWAP
<0
V 1B
>0
ACTIVE POINT – INACTIVE INPUT
operation of the ADE7761B in this mode, the V DD pin of the
ADE7761B must be maintained within the specified range
(5 V ± 5%). The missing neutral detection algorithm is designed
to work over a line frequency of 45 Hz to 55 Hz.
6.25% OF INACTIVE INPUT
Figure 29. Fault Conditions for Inactive Input Greater Than Active Input
Rev. 0 | Page 18 of 24
相关PDF资料
PDF描述
ADE7768ARZ-RL IC ENERGY METERING 1PHASE 16SOIC
ADE7769ARZ-RL IC ENERGY METERING 1PHASE 16SOIC
ADM8843ACPZ-REEL7 IC LED DRVR WHITE BCKLGT 16LFCSP
ADP1653ACPZ-R7 IC LED DRVR PHOTO FLASH 16-LFCSP
ADP1712-EVALZ BOARD EVALUATION ADP1712
相关代理商/技术参数
参数描述
ADE7762 制造商:AD 制造商全称:Analog Devices 功能描述:Polyphase Energy Metering IC with Phase Drop Indication
ADE7762ARW 制造商:AD 制造商全称:Analog Devices 功能描述:Polyphase Energy Metering IC with Phase Drop Indication
ADE7762ARW-RL 制造商:AD 制造商全称:Analog Devices 功能描述:Polyphase Energy Metering IC with Phase Drop Indication
ADE7762ARWZ 功能描述:IC ENERGY METERING 3PHASE 28SOIC RoHS:是 类别:集成电路 (IC) >> PMIC - 能量测量 系列:- 产品培训模块:Lead (SnPb) Finish for COTS Obsolescence Mitigation Program 标准包装:2,500 系列:*
ADE7762ARWZ-RL 功能描述:IC ENERGY METERING 3PHASE 28SOIC RoHS:是 类别:集成电路 (IC) >> PMIC - 能量测量 系列:- 产品培训模块:Lead (SnPb) Finish for COTS Obsolescence Mitigation Program 标准包装:2,500 系列:*