5.0 R EVIEWING
THE
F RONT B UTTONS
AND
D ISPLAY
SEL
RST
KEY
SEL
RST
DISPLAY MODE OPERATION
Index display through enabled values
Resets count display(s) and/or outputs
ENTERING PROGRAM MODE
Press and hold for 2 seconds to activate
PROGRAMMING MODE OPERATION
Store selected parameter and index to next parameter
Advances through the program menu/
Increments selected parameter value or selection
OPERATING MODE DISPLAY DESIGNATORS
“ R ” - To the left of the display is the rate value.
- Counter A has no designator.
“ b ” - To the left of the display is the Counter B value (dual count or batch).
“1” and “2” - Indicates setpoint 1 and 2 output status.
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between
the rate and count values.
6.0 P ROGRAMMING
THE
M ETER
DISPLAY
MODE
SEL
NO
OVERVIEW
PROGRAMMING MENU
Pro
Input Setup
Parameters
RST
SEL
1-INPUt
Rate Setup
Parameters
SEL
2-rAtE
Display and Front
Panel Key
Parameters
SEL
3-dSPLAY
Setpoint
Output
Parameters
SEL
4-SEtPt
Serial
Setup
Parameters
SEL
5-SEriAL
INP A-b ?
? Cnt ud
PROGRAMMINGMODEENTRY(SELKEY)
It is recommended all programming changes be made off line, or before
installation. The meter normally operates in the Display Mode. No parameters
can be programmed in this mode. The Programming Mode is entered by
pressing and holding the SEL key. If it is not accessible then it is locked by
either a security code, or a hardware lock.
MODULE ENTRY (SEL & RST KEYS)
The Programming Menu is organized into separate modules. These modules
group together parameters that are related in function. The display will alternate
between Pro and the present module. The RST key is used to select the desired
module. The displayed module is entered by pressing the SEL key.
MODULE MENU (SEL KEY)
Each module has a separate module menu (which is shown at the start of each
module discussion). The SEL key is pressed to advance to a particular parameter
to be changed, without changing the programming of preceding parameters.
After completing a module, the display will return to Pro NO . Programming may
continue by accessing additional modules.
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and
the selections/value for that parameter. The RST key is used to move through the
selections/values for that parameter. Pressing the SEL key, stores and activates the
displayed selection/value. This also advances the meter to the next parameter.
For numeric values, press the RST key to access the value. The right hand
most digit will begin to flash. Pressing the RST key again increments the digit
by one or the user can hold the RST key and the digit will automatically scroll.
The SEL key will advance to the next digit. Pressing and holding the SEL key
will enter the value and move to the next parameter.
6
PROGRAMMING MODE EXIT (SEL KEY)
The Programming Mode is exited by pressing the SEL key with Pro NO
displayed. This will commit any stored parameter changes to memory and
return the meter to the Display Mode. (If power loss occurs before returning to
the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
It is recommended to start with Module 1 for counting or Module 2 for rate.
When programming is complete, it is recommended to record the parameter
programming and lock out parameter programming with the user input or
programming security code.
FACTORY SETTINGS
Factory settings may be completely restored in Module 3. This is useful when
encountering programming problems.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will
appear. This is used to illustrate the display alternating between the parameter
on top and the parameter ’s factory setting on the bottom. In most cases,
selections and values for the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
Selection/Value
Factory Settings are shown.
相关PDF资料
PDF描述
CUB5TB00 TIMER & CYCLE COUNTER W/BKLT
CUB7P200 HSPEED LOGIC INPUT CNTR POS
CUB7T000 TIMER LCD PROGRAM 8 DIGIT
CUB7W020 COUNTER 8-DIGIT RED BKLT VOLT-IN
D-659-0001 TOOL REMOVAL MTC CONN WAFER
相关代理商/技术参数
参数描述
CUB5RTB0 制造商:Red Lion Controls 功能描述:PANEL METER; RTD METER WITH RED/GREEN BACKLIGHT DISPLAY 制造商:Red Lion Controls 功能描述:RTD METER WITH RED/GREEN 制造商:Red Lion Controls 功能描述:TEMPERATURE DISPLAY FOR RTD 制造商:Red Lion Controls 功能描述:PANEL DISPLAY, TEMPERATURE, 95mA, 9V TO 28V; No. of Digits / Alpha:5; Meter Function:Temperature; Meter Range:-19999 to +19999; Digit Height:12.2mm; Panel Cutout Height:39.1mm; Panel Cutout Width:74.9mm
CUB5RTR0 功能描述:RTD METER REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5SNK0 功能描述:DUAL SINKING OPEN OC OUT CARD RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5TB00 功能描述:TIMER & CYCLE COUNTER W/BKLT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:* 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB5TCB0 功能描述:METER PANEL LCD THERMOCOUPLE RED RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:CUB5 标准包装:12 系列:* 其它名称:Q7072030