Program Mode Lock-out
See Programming Mode Access chart.
(Module 3)
SCALINGFORCOUNTINDICATION
The CUB5’s scale factor is factory set to 1, to provide one count on the
display for each pulse that is input to the unit. In many applications, there will
not be a one-to-one correspondence between input pulses and display units.
Therefore, it is necessary for the CUB5 to scale or multiply the input pulses by
a scale factor to achieve the desired display units (feet, meters, gallons, etc.)
The Count Scale Factor Value can range from 00.0001 to 99.9999. It is
important to note that the precision of a counter application cannot be improved
by using a scale factor greater than one. To accomplish greater precision, more
pulse information must be generated per measuring unit. The following formula
is used to calculate the scale factor.
? NO
DISPLAY MODE DESCRIPTION
Pro Loc
USER INPUT FUNCTION
USEr INP ?
NO No Function User Input disabled.
Inhibit Inhibit Inhibit counting for the selected counter(s).
Scale Factor = Desired Display Units x Decimal Point Position
Number of Pulses
WHERE:
Desired Display Units : Count display units acquired after pulses that occurred.
Number of Pulses : Number of pulses required to achieve the desired
display units.
Decimal Point Position :
0 = 1
0.0 = 10
0.00 = 100
0.000 = 1000
0.0000 = 10000
0.00000 = 100000
rESEt
StorE
Stor-rSt
d-SELECt
d-LEVEL
d-COLOr
Print
Prnt-r5t
rESEt-1
Maintained Reset
Store
Store and Reset
Display Select *
Display Intensity Level *
Backlight Color *
Print Request
Print and Reset *
Setpoint 1 Reset *
Level active reset of the selected counter(s).
Freeze display of selected counter(s) while
allowing counts to accumulate internally.
Edge triggered reset of the selected
counter(s) after storing the count.
Advance once for each activation
Increase intensity one level for each
activation. (backlight version only)
Change backlight color with each activation
(backlight version only)
Serial transmit of the active parameters
selected in the Print Options (Module 5)
Same as Print Request followed by a
momentary reset of the selected counter(s).
Reset Setpoint 1 output
Scale Factor = Desired Display Units x Decimal Point Position
EXAMPLE :  The counter display is used to indicate the total number of feet
used in a process. It is necessary to know the number of pulses for the desired
units to be displayed. The decimal point is selected to show the resolution in
hundredths.
Number of Pulses
rESEt-2 Setpoint 2 Reset * Reset Setpoint 2 output
rESEt-12 Setpoint 1 and 2 Reset * Reset Setpoint 1 and 2 outputs
Note: * indicates Edge Triggered function. Other functions are Level Active
(maintained)
Scale Factor = 1.00 x 100
Given that 128 pulses are equal to 1 foot, display total feet with a one-
hundredth resolution.
128
Scale Factor = 0.007812 x 100
Scale Factor = 0.7812
USER INPUT ASSIGNMENT
USEr ASN ? Count A Count b
? Count A
both A-b
The User Input Assignment is only active when Counter B is enabled and the
User Input performs a Reset, Inhibit or Store function on one or both counters.
6.2 MODULE 2 - R ATE S ETUP P ARAMETERS ( 2-rAtE )
2-rAtE
SEL
PARAMETER MENU
Pro
RAtE Enb
Rate
Enable
RAtE dP
Rate Decimal
Point
RAtE dSP
Rate Scaling
Display Value
RAtE INP
Rate Scaling
Input Value
LO-Udt
Rate Low
Update Time
HI-Udt
Rate High
Update Time
?
Module 2 is the programming for the rate parameters. For maximum input
frequency, Rate Enable should be set to NO when not in use. When set to NO , the
remaining rate parameters are not accessible. The rate value is shown with an
annunciator of “ R ” in the Display Mode.
RATE ENABLE
RAtE Enb ?
NO YES
YES
RATE SCALING DISPLAY VALUE
RAtE dSP ? 0 to 999999
? 001000
Enter the desired Rate Display Value for the Scaling Point.*
RATE SCALING INPUT VALUE
RAtE dP
?
?
O
RATE DECIMAL POINT
0 0.00
0.0 0.000
0.0000
0.00000
RAtE INP ? 0.1 to 99999.9
? 01000.0
Enter the corresponding Rate Input Value for the Scaling Point.*
This selects the decimal point position for the rate display and any setpoint
value assigned to rate. This parameter does not affect rate scaling calculations.
8
*For value entry instructions, refer to selection/value entry in the Programming
The Meter section.
相关PDF资料
PDF描述
MLBAWT-A1-0000-000W50 LED XLAMP ML-B WHITE SMD
MLBAWT-A1-0000-000VF8 LED XLAMP ML-B WHITE SMD
MLBAWT-A1-0000-000VF7 LED XLAMP ML-B WHITE SMD
ACA-20RM-5-AC4-RL-ALM-C AMMETER AC 30A 220V W/ALARM RED
MLBAWT-A1-0000-000VF5 LED XLAMP ML-B WHITE SMD
相关代理商/技术参数
参数描述
CUB5TB00 功能描述:TIMER & CYCLE COUNTER W/BKLT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:* 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB5TCB0 功能描述:METER PANEL LCD THERMOCOUPLE RED RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:CUB5 标准包装:12 系列:* 其它名称:Q7072030
CUB5TCR0 功能描述:THERMO METER REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5TR00 制造商:Red Lion Controls 功能描述:PRESET TIMR & CYCLE COUNTR W/REFL DSPLY 制造商:Red Lion Controls 功能描述:TIMER, ELECTRONIC , 8DIGIT, 9V TO 28V; Supply Voltage Range:9V DC to 28V DC; Panel Cutout Height:39.1mm; Panel Cutout Width:74.9mm; Time Range:- ;RoHS Compliant: Yes
CUB5USB0 功能描述:USB OPTION CARD RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030