5.0 R EVIEWING
THE
F RONT B UTTONS
AND
D ISPLAY
1
SEL
RST
KEY
SEL
RST
DISPLAY MODE OPERATION
Select display (timer or cycle counter)
Reset value(s) per Front Panel Reset setting
ENTERING PROGRAM MODE
Press and hold for 2 seconds to activate
PROGRAMMING MODE OPERATION
Store selected parameter and index to next parameter
Advances through the program menu
Increments selected parameter value or selection
OPERATING MODE DISPLAY DESIGNATORS
“ t ” - To the left of the display is the timer value.
“1” - To the upper left of the display indicates the setpoint status.
“ C ” - To the left of the display is the cycle counter value.
If display scroll is enabled, the display will toggle automatically every four seconds between the timer and cycle counter values.
6.0 P ROGRAMMING
THE
M ETER
DISPLAY
MODE
SEL
OVERVIEW
PROGRAMMING MENU
NO
Display and Front
Setpoint
Serial
Timer Input
Parameters
Cycle Counter
Parameters
Panel Key
Parameters
Output
Parameters
Setup
Parameters
Pro
RST
SEL
1-INPUt
SEL
2-Count
SEL
3-dSPLAY
SEL
4-SEtPt
SEL
5-SEriAL
PROGRAMMING MODE ENTRY (SEL KEY)
It is recommended all programming changes be made off line, or before
installation. The meter normally operates in the Display Mode. No parameters
can be programmed in this mode. The Programming Mode is entered by
pressing and holding the SEL key. If it is not accessible, then it is locked by
PROGRAMMING MODE EXIT (SEL KEY)
The Programming Mode is exited by pressing the SEL key with ?????? ?
displayed. This will commit any stored parameter changes to memory and
return the meter to the Display Mode. (If power loss occurs before returning to
the Display Mode, verify recent parameter changes.)
either a security code, or a hardware lock (See Module 3).
PROGRAMMING TIPS
MODULE ENTRY (SEL & RST KEYS)
The Programming Menu is organized into separate modules. These modules
group together parameters that are related in function. The display will alternate
between ??? and the present module. The RST key is used to select the desired
It is recommended to start with Module 1 and proceed through each module
in sequence. When programming is complete, it is recommended to record the
parameter programming and lock out parameter programming with the user
input or programming security code.
module. The displayed module is entered by pressing the SEL key.
FACTORY SETTINGS
INPUt s OP ?
? LEVEL
MODULE MENU (SEL KEY)
Each module has a separate module menu (which is shown at the start of each
module discussion). The SEL key is pressed to advance to a particular parameter
to be changed, without changing the programming of preceding parameters.
After completing a module, the display will return to ???? ?? . Programming
may continue by accessing additional modules.
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and
the selections/value for that parameter. The RST key is used to move through the
selections/values for that parameter. Pressing the SEL key, stores and activates the
displayed selection/value. This also advances the meter to the next parameter.
For numeric values, press the RST key to access the value. The right hand
most digit will begin to flash. Pressing the RST key again increments the digit
by one or the user can hold the RST key and the digit will automatically scroll.
The SEL key will advance to the next digit. Pressing and holding the SEL key
will enter the value and move to the next parameter.
6
Factory Settings may be completely restored in Module 3. This is useful
when encountering programming problems.
Pressing the RST key on power-up will load the factory settings and display
rESEt . This allows operation in the event of a memory failure or corrupted data.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will
appear. This is used to illustrate the display alternating between the parameter
on top and the parameter ’s Factory Setting on the bottom. In most cases,
selections and values for the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
Selection/Value
Factory Settings are shown.
相关PDF资料
PDF描述
CUB7P200 HSPEED LOGIC INPUT CNTR POS
CUB7T000 TIMER LCD PROGRAM 8 DIGIT
CUB7W020 COUNTER 8-DIGIT RED BKLT VOLT-IN
D-659-0001 TOOL REMOVAL MTC CONN WAFER
D7-1 DIE, .041 HOLE DIA
相关代理商/技术参数
参数描述
CUB5TCB0 功能描述:METER PANEL LCD THERMOCOUPLE RED RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:CUB5 标准包装:12 系列:* 其它名称:Q7072030
CUB5TCR0 功能描述:THERMO METER REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5TR00 制造商:Red Lion Controls 功能描述:PRESET TIMR & CYCLE COUNTR W/REFL DSPLY 制造商:Red Lion Controls 功能描述:TIMER, ELECTRONIC , 8DIGIT, 9V TO 28V; Supply Voltage Range:9V DC to 28V DC; Panel Cutout Height:39.1mm; Panel Cutout Width:74.9mm; Time Range:- ;RoHS Compliant: Yes
CUB5USB0 功能描述:USB OPTION CARD RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5VB00 功能描述:DC VOLTMETER RED/GREEN BKLT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030