Multi-channel Controller/Pressure Sensor
Function Details
Series
PSE530/200
A Display calibration function
This function eliminates slight differences in the output values of all 4
channels and allows uniformity in the numbers displayed. Displayed
values of the pressure sensors can be adjusted to within ± 5%.
± 5% R.D.
B Copy function
Information that can be copied includes the following: q Pressure set
values, w Range settings, e Display Units, r Output modes, t
Response times.
? When CH1 is copied to CH2, CH3, and CH4, information of OUT1 in
CH1 will be copied.
? When CH2, CH3, or CH4 is copied to CH1, information of OUT1 in CH2,
0
+
Applied pressure
Displayed value at the time of shipment
Adjustable range of display calibration function
CH3, or CH4 will be copied only to OUT1 in CH1.
Note) When the copy function is used, the regulating pressure value of
the copied channel may change ± 1 digit.
ZSE ?
ISE ?
PSE
Z
SE3
I
Note) When the display calibration function is used, the regulating pressure
value may change ± 1 digit.
PS
C Auto shift function
When auto shift is NOT used:
When the supply pressure fluctuates, a correct sensing is no longer possible.
Z
I
SE 12
If there is a fluctuation in the supply pressure, erroneous operation may
occur (e.g., in the case of adsorption verification, the switch does not turn
ON even though the workpiece is being adsorbed, or does not turn OFF
even though the workpiece is no longer being adsorbed.)
The auto shift function rectifies pressure changes to ensure proper
ON/OFF switch response during such fluctuations.
Pressure ↑
P1
Set value
P2
Supply pressure
normal
Supply pressure
drop
Supply pressure
increase
ZSP
ISA2
IS ?
<Principle>
At the point when the supply pressure fluctuates, the set pressure value is
rectified by setting the auto shift input (external input) to Lo (no-voltage
input), using the pressure measured at that point as a standard.
? This function is good only for those channels whose function selection is
turned “on” during the auto shift mode setting.
? Maintain the constant pressure for 10 ms or more after a drop in the auto
Switch output ON
1&2
OFF
When auto shift is used:
Does not turn ON
Set value Set value
rectification rectification
Time →
Does not turn OFF
Time →
ZSM
PF2 ?
IF ?
shift input.
? When the auto shift is input, “ooo” will be displayed for approximately 1
second, and the pressure value at that point will be saved as a rectified
Pressure ↑
Supply pressure
normal
Supply pressure
drop
Supply pressure
increase
Data
value “C_5” (for CH1) or “C_3” (for CH2 and CH3). Based on the saved
rectified values, the set value “P_1” to “P_4” or “n_1” to “n_4” will likewise
be rectified.
Set value
P1
P2
OFF
? The time from the moment the auto shift is input, to the moment the
switch output actually operates is 15 ms or less.
? If the set value rectified by the auto shift input exceeds the regulating
pressure range, it will be rectified once more to within the values of the
regulating pressure range.
Switch output ON
1&2
Time →
? When the auto shift function is turned “off ”, the shift value will be zero.
? When all of the auto shift functions are turned “off ”, “ooo” will not be
10 ms or more
15 ms
or less
(
Time →
Switch output
response time when
auto shift is input.
)
displayed even if the auto shift input is set to Lo (no-voltage input).
Hi
? Values “C_5” and “C_3”, rectified after the auto shift is input, will be lost
once the power is turned off.
? Values “C_5” and “C_3”, rectified after the auto shift function is used, will
Auto shift
input
Lo
be reset to zero (initial value) when the power is turned back on again.
Note) Rectified values are not saved in EEPROM.
D Auto identification function
E Unit display switching function
Display units can be switched with this function.
Units that can be displayed vary depending on the range of the pressure
sensors connected to the controller.
This function automatically identifies the pressure range of the pressure
sensor that is connected to the multi-channel pressure sensor controller,
thus eliminating the need of having to reset the range again after
Display units can be selected using either
Unit Display and Resolution
or
.
replacing the sensor. This function will be activated either when “Aon” is
Applicable pressure sensor
PSE530
PSE531
PSE532
PSE533
set in the auto identification mode or when the power is turned back on in
that condition. However, this function only works in conjunction with
specific pressure sensors (SMC Series PSE53 ). When other pressure
Regulating pressure range –0.1 to 1 MPa 10 to –101 kPa –10 to 101 kPa –101 to 101 kPa
kPa — 0.1 0.1 0.1
sensors are used, this function will not work. When using other types of
pressure sensors, first set the auto identification mode to “AoF”, and then
proceed to setting the range. Turning the power back on while in the “Aon”
setting can cause a malfunction.
MPa
kgf/cm 2
bar
psi
mmHg
inHg
0.001
0.01
0.01
0.1
0.001
0.001
0.01
1
0.1
0.001
0.001
0.01
0.001
0.001
0.02
1
0.1
16-3-17
相关PDF资料
PDF描述
XPCRED-L1-0000-00401 LED RED XLAMP CLR SMD
CLN6A-WKW-CK0L0343 LED COOL WHITE 5X5MM SMD
MX3SWT-A1-0000-000E51 LED COOL WHITE 6500K XLAMP SMD
MX6AWT-A1-R250-000BE3 LED XLAMP COOL WHITE 5000K SMD
CLN6A-MKW-CJ0K0233 LED WARM WHITE 5X5MM SMD
相关代理商/技术参数
参数描述
PSE201-A4C 制造商:SMC Corporation of America 功能描述:CONTROLLER, PRESSURE SENSOR 制造商:SMC 功能描述:Multi-channel digital sensor controller
PSE22 制造商:SCHURTER 制造商全称:Schurter Inc. 功能描述:Snap-in switch for switches PSE, MSM and MCS 30
PSE24-105 制造商:POWERSOLVE 功能描述:PSU DESKTOP 5V 3A
PSE24-105 制造商:POWERSOLVE 功能描述:PSU DESKTOP 5V 3A
PSE24-209 制造商:POWERSOLVE 功能描述:PSU DESKTOP 9V 2.4A