参数资料
型号: LD4006P0
厂商: Red Lion Controls
文件页数: 13/16页
文件大小: 0K
描述: COUNTER 6 DIGIT DUAL 4.0" RED
标准包装: 1
系列: LD
计数速率: 35kHz
数字/字母数: 6
输入类型: 电压、开关外壳、晶体管开关
输出类型: 继电器和 RS232/RS485
电源电压: 11 V ~ 16 VDC,85 V ~ 250 VAC
显示器类型: LED 红
5.5 MODULE 5 - S ERIAL C OMMUNICATIONS P ARAMETERS ( ????? )
5-SEr
PAR
PARAMETER MENU
Pro
bAUd
Baud Rate
dAtA
Data Bit
PAritY
Parity Bit
Addr
Meter
Abbr
Abbreviated
Pr-OPt
Print
AUtO
Automatic
COPY
Copy
Address
Printing
Options
Data
Program
Transmit
Settings
Module 5 is the programming module for the Serial Communications
PRINT OPTIONS
Parameters. These parameters are used to match the serial settings of the meter
with those of the host computer or other serial device.
?????? ?
?
??
??
???
BAUD RATE
This parameter selects the meter values transmitted in response to a Print
????
?
?
????
???
???
????
????
????
????
?????
?????
Request. A print request is also referred to as a block print because more than
one parameter can be sent to a printer or computer as a block.
Selecting ??? ? displays a sublist for choosing the meter parameters to appear
in the print block. All active parameters entered as ??? in the sublist will be
Set the baud rate to match that of other serial communications equipment.
Normally, the baud rate is set to the highest value that all of the serial
communications equipment is capable of transmitting and receiving.
DATA BIT
transmitted during a block print. Parameters entered as ?? will not be sent.
The “Print All” ( ?????? ) option selects all meter values for transmitting
( ??? ), without having to individually select each parameter in the sublist.
Note: Inactive parameters will not be sent regardless of the print option
setting. For example, Counter B or Scale Factor B will only be sent if Counter
B is enabled (Dual Counter mode or batch count). Likewise, the Rate value will
not be sent unless the Rate Display is enabled.
???? ?
? ?????
????? ?????
DISPLAY
???? ?
???? ?
DESCRIPTION
Counter A
Counter B
FACTORY
SETTING
???
??
MNEMONIC
CTA
CTB
Select either 7- or 8-bit data word length. Set the word length to match the
other serial communications equipment on the serial link.
????
???? ?
???? ?
Rate Value
Scale Factor A
Scale Factor B
??
??
??
RTE
SFA
SFB
?????? ?
?
PARITY BIT
??
???
??? ????
This parameter only appears when the Data Bit parameter is set to a 7-bit
data word length. Set the parity bit to match that of the other serial equipment
on the serial link. The meter ignores parity when receiving data and sets the
parity bit for outgoing data. If parity is set to ?? , an additional stop bit is used
to force the frame size to 10 bits.
????
?
???? Setpoint 1 ??
???? Setpoint 2 ??
???? ?? Counter A Count Load ??
AUTOMATIC DATA TRANSMIT
? ?? ???
??
SP1
SP2
CLD
Selecting ??? causes the meter to automatically transmit serial data per the
Print Options selection list. This occurs without using the User Input terminal
METER ADDRESS
Print Request function (Module 1), and without requiring any serial data request
commands. This makes the User Input available to perform other functions,
????
?
?
??
?
to
??
while still allowing the meter to output serial data.
The selected data is transmitted repeatedly every 1.5 seconds during normal
operating mode, and pauses during programming mode.
Enter the serial node address. With a single unit, an address is not needed
and a value of zero can be used (RS232 applications). Otherwise, with multiple
COPY PROGRAM SETTINGS
bussed units, a unique address number must be assigned to each meter. The
node address applies specifically to RS485 applications.
????
?
?
??
??
???
????
?
?
??
ABBREVIATED PRINTING
?? ???
This parameter is used to copy all the program settings from one LD meter
directly to another LD meter(s), through the serial terminal block connections
(RS232 or RS485). No PC connection or additional software is required.
Copying program setttings eliminates or greatly reduces programming time
when multiple meters use identical, or very similar, settings for an application.
This parameter determines the formatting of data transmitted from the meter
in response to a Transmit Value command or a Block Print Request. Select ?? ?
for a full print transmission, consisting of the meter address, mnemonics, and
parameter data. Select ??? for abbreviated print transmissions, consisting of the
parameter data only. This setting is applied to all the parameters selected in the
PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent
during a full transmission.)
13
Copy Requirements :
To copy program settings from one meter to another requires the following:
1. Each meter must have the same software version. The version is displayed
during the meter power-up sequence, or by entering Code 50 in the Factory
Service Operations. (See Module 3 for details)
2. Each meter receiving the program settings (receiver) must have the baud rate
相关PDF资料
PDF描述
LD412460 DIODE MOD ISO DUAL 2400V 600A
LIRT220A CONTROL RELAY CURRENT 220VAC
LNXC2000 COUNTER DUAL PRESET 115VAC
LP-56-850 XFRMR 115/230V 28V 1.7A 48VA PCB
LS412460 DIODE MOD ISO SGL 2400V 600A
相关代理商/技术参数
参数描述
LD400-AC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform
LD400-DC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform
LD400L-2AC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform
LD400L-2DC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform
LD400L-AC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform