参数资料
型号: LD4006P0
厂商: Red Lion Controls
文件页数: 14/16页
文件大小: 0K
描述: COUNTER 6 DIGIT DUAL 4.0" RED
标准包装: 1
系列: LD
计数速率: 35kHz
数字/字母数: 6
输入类型: 电压、开关外壳、晶体管开关
输出类型: 继电器和 RS232/RS485
电源电压: 11 V ~ 16 VDC,85 V ~ 250 VAC
显示器类型: LED 红
set to 9600 baud. This is the factory default setting, so a new meter should
arrive ready for copying. The meter sending the program settings (master)
should be set to the desired baud rate for the application (if different than
9600). This baud rate setting will then be copied to the receiver(s).
Copy Connections :
To connect the LD meters for copying, refer to section 3.5 Serial Wiring for
details. The meter shown in the figures as LD METER will be the master.
1. RS232 - Allows copying from the master meter to a single receiver only.
2. RS485 - Allows copying from the master meter to one or more receivers
simultaneously. Up to 31 receiving meters can be connected during copying.
Sending Serial Commands and Data
When sending commands to the meter, a string containing at least one
Copy Procedure :
1. Connect the master and receiver(s) using RS232 or RS485 terminals.
2. Apply power to the meters. The receiving meter(s) must be operating in the
normal display mode (not programming mode).
3. On the master meter, proceed to the Copy Program Settings parameter and
select ??? to begin copying.
4. During the copy process (~ 2 sec.), the master meter displays an upload message
( ????? ) while the receiver(s) displays a download message ( ????? ). This
indicates successful communication between the master and receiver(s).
5. When copying is completed, all receivers display the power-up sequence and
return to normal operating mode, programmed with all the same settings as
the master meter. The master remains at the ???? prompt, ready for another
receiver(s) to be connected for copying.
Register Identification Chart
command character must be constructed. A command string consists of a
command character, a value identifier, numerical data (if writing data to the
meter) followed by a command terminator character, * or $.
Command Chart
ID
A
B
Value Description
Counter A
Counter B
MNEMONIC
CTA
CTB
Applicable
Commands
T, V, R
T, V, R
Transmit Details (T and V)
6 digit positive/5 digit
negative (with minus sign)
5 digit, positive only
Command Description
Notes
C
Rate
RTE
T
5 digit, positive only
N
T
Node (meter)
Address Specifier
Transmit Value (read)
Address a specific meter. Must be followed
by one or two digit node address. Not
required when node address = 0.
Read a register from the meter. Must be
followed by a register ID character.
D
E
F
Scale Factor A
Scale Factor B
Setpoint 1
(Reset Output 1)
SFA
SFB
SP1
T, V
T, V
T, V, R
6 digit, positive only
6 digit, positive only
per setpoint Assignment,
same as Counter or Rate
V
Write to register of the meter. Must be
Value Change (write) followed by a register ID character and
G
Setpoint 2
(Reset Output 2)
SP2
T, V, R
per setpoint Assignment,
same as Counter or Rate
R
Reset
numeric data.
Reset a count value or setpoint output. Must
be followed by a register ID character
H
Counter A Count
Load Value
CLD
T, V, R
6 digit positive/5 digit
negative (with minus sign)
P
Block Print Request
(read)
Initiates a block print output. Registers in the
print block are selected in Print Options.
Command String Examples:
1. Node address = 17, Write 350 to the Setpoint 1 value
Command String Construction
The command string must be constructed in a specific sequence. The meter
does not respond with an error message to illegal commands. The following
procedure details construction of a command string:
1. The first 2 or 3 characters consist of the Node Address Specifier (N) followed
by a 1 or 2 character node address number. The node address number of the
meter is programmable. If the node address is 0, this command and the node
address itself may be omitted. This is the only command that may be used in
conjunction with other commands.
2. After the optional address specifier, the next character is the command
character.
3. The next character is the register ID. This identifies the register that the
command affects. The P command does not require a register ID character. It
prints all the active selections chosen in the Print Options menu parameter.
4. If constructing a value change command (writing data), the numeric data is
sent next.
5. All command strings must be terminated with the string termination
characters * or $. The meter does not begin processing the command string
until this character is received. See timing diagram figure for differences in
meter response time when using the * and $ terminating characters.
Receiving Data From The Meter
Data is transmitted from the meter in response to either a transmit command
(T), a block print request command (P) or a User Input print request. The
response from the meter is either a full field transmission or an abbreviated
transmission, depending on the selection chosen in Module 5.
Full Field Transmission
String: N17VF350*
2. Node address = 5, Read Counter A, response time of 50 msec min
String: N5TA*
3. Node address = 0, Reset Setpoint 1 output
String: RF*
4. Node address = 31, Request a Block Print Output, response time of 2 msec min
String: N31P$
Transmitting Data to the Meter
Numeric data sent to the meter must be limited to transmit details listed in the
Register Identification Chart. Leading zeros are ignored. Negative numbers
must have a minus sign. The meter ignores any decimal point and conforms the
number to the scaled resolution. (For example: The meter ’s scaled decimal point
position is set for 0.0 and 25 is written to a register. The value of the register is
now 2.5. In this case, write a value of 250 to equal 25.0).
Note: Since the meter does not issue a reply to value change commands, follow
with a transmit value command for readback verification.
The first two characters transmitted are the meter address. If the address
assigned is 0, two spaces are substituted. A space follows the meter address field.
The next three characters are the register mnemonic, as shown in the Register
Identification Chart.
The numeric data is transmitted next. The numeric field (bytes 7 to 18) is 12
characters long. When a requested counter or rate value exceeds the meter ’s
Byte
1, 2
3
4-6
7-18
19
20
21
22
23
Description
2 byte Node Address field [00-99]
<SP> (Space)
3 byte Register Mnemonic field
12 byte data field; 10 for number, one for sign, one for decimal point
<CR> (carriage return)
<LF> (line feed)
<SP>* (Space)
<CR>* (carriage return)
<LF>* (line feed)
display limits, an * (used as an overflow character) replaces a space in byte 7.
Byte 8 is always a space.
The remaining ten positions of this field consist of a minus sign (for negative
values), a floating decimal point (if applicable), and eight positions for the
requested value. The data within bytes 9 to 18 is right-aligned with leading
spaces for any unfilled positions.
The end of the response string is terminated with a <CR> and <LF>. After the
last line of a block print, an extra <SP>, <CR> and <LF> are added to provide
separation between the print blocks.
* These characters only appear in the last line of a block print.
14
相关PDF资料
PDF描述
LD412460 DIODE MOD ISO DUAL 2400V 600A
LIRT220A CONTROL RELAY CURRENT 220VAC
LNXC2000 COUNTER DUAL PRESET 115VAC
LP-56-850 XFRMR 115/230V 28V 1.7A 48VA PCB
LS412460 DIODE MOD ISO SGL 2400V 600A
相关代理商/技术参数
参数描述
LD400-AC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform
LD400-DC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform
LD400L-2AC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform
LD400L-2DC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform
LD400L-AC 制造商:MRV 制造商全称:MRV 功能描述:LambdaDriver Chassis - DWDM/CWDM Platform